ABB ACS355 Manual page 53

Solar pump inverter (+n827)
Hide thumbs Also See for ACS355:
Table of Contents

Advertisement

All parameters
No.
Name/
Value
2621
SMOOTH
START
NO
ALWAYS
START ONLY
2622
SMOOTH
START CUR
10...100%
Description
Selects the forced current vector rotation mode at low
speeds. When the smooth start mode is selected, the
rate of acceleration is limited by the acceleration and
deceleration ramp times (parameters
[see ACS355 User's manual (3AUA0000066143
[English])]). If the process driven by the permanent
magnet synchronous motor has high inertia, slow
ramp times are recommended.
Can be used for permanent magnet synchronous
motors only (see chapter Appendix: Permanent
magnet synchronous motors (PMSMs) in ACS355
User's manual (3AUA0000066143 [English])).
Disabled
Enabled always when the frequency is below the
smooth start frequency (parameter 2623 SMOOTH
STARTFRQ). See ACS355 User's manual
(3AUA0000066143 [English]).
Enabled below the smooth start frequency (parameter
2623 SMOOTH START FRQ) only when starting the
motor.
Defines the current used in the current vector rotation
at low speeds. Increase the smooth start current if the
application requires high pull-up torque. Decrease the
smooth start current if motor shaft swinging needs to
be minimized. Note that accurate torque control is not
possible in the current vector rotation mode.
This parameter can be used for permanent magnet
synchronous motors only (see chapter Appendix:
Permanent magnet synchronous motors (PMSMs) in
ACS355 User's manual (3AUA0000066143
[English])).
Value as a percentage of the nominal motor current.
Actual signals and parameters 53
2202
and 2203
Def/ FbEq
ALWAYS
0
1
2
10%
1 = 1%