ABB ACS355 Manual page 55

Solar pump inverter (+n827)
Hide thumbs Also See for ACS355:
Table of Contents

Advertisement

All parameters
No.
Name/
Value
60 PUMP CONTROL
6001
AUTO/MANUAL
SEL
AUTO
MANUAL
6002
MANUAL
START CMD
DI1
DI2
DI3
DI1P, 2P
6003
START DC
VOLT
109...800 V
Description
Defines pump control parameters.
Selects the start mode of the inverter.
Inverter starts automatically if DC bus voltage is more
than the 6003 START DC VOLT.
Note: If the timed function is enabled in parameter
3601 TIMERS ENABLE, then the drive starts as per
the timed function configuration. For more details of
timed function, see group 36 TIMED FUNCTIONS in
ACS355 User's manual (3AUA0000066143 [English]).
Inverter starts when the manual start command is on.
See parameter 6002 MANUAL START CMD.
Defines the source for inverter to start in manual
mode. The selection is effective when parameter 6001
is MANUAL and the inverter is in remote control mode.
Start and stop through digital input DI1.
0 = Stop, 1 = Start
Start and stop through digital input DI2.
0 = Stop, 1 = Start
Start and stop through digital input DI3.
0 = Stop, 1 = Start
Pulse starts through digital input DI1.
0 -> 1: Start.
Pulse stops through digital input DI2. 1 -> 0: Stop
Note: To start the inverter, activate DI2 prior to feeding
pulse to DI1.
Defines the minimum DC voltage to start the inverter.
Note: If you change this value while the inverter is
running, the changed value is effective only during the
next start.
DC voltage.
Note: Range is different for 1-phase and 3-phase
inverters.
Actual signals and parameters 55
Def/ FbEq
MANUAL
0
1
DI1
0
1
2
3
1 = 1 V
400 V unit:
225
200 V unit:
129