Counters
Up to 16 User Counters are available and can be used as a part of the Events system. User
Counters can be set up as a Cause or an Effect of an Event. A Counter Effect can be used
to count an occurence or to reset different types of counters depending on hardware avail-
ability. Other counters available are Alarm, Event, Digital Input, Relay Output and Pulse
counters.
Other Standard features ..
36
Functions and Features
• CE Mark - Conformity with 73/23/EEC, Low Voltage and 89/336/EEC EMC Directive.
• Soft Alarms - 6 "software" alarms per pen are easily set up to display and record selected
out-of-limit conditions. These can be tied to the relay or digital outputs to activate the user's
external equipment.
• Common Relay Output - A separate relay output at the rear of the unit can be set up as an
alarm output. (Not available for the SIREC D200 recorder).
• Communications - the recorder supports FTP, Modbus TCP/IP (slave mode), Web and E-
mail over Ethernet (DHCP standard) communications port and Modbus RTU (slave mode)
via an RS485 port. USB ports allow the use of an ASCII barcode reader. (RS485 port is an
option for the SIREC D200 recorder). Email sent to your network connected PC triggered
by an Alarm or an Event.
• Independent Display Chart Speeds and Logging rates - logging rates can be pro-
grammed completely separate from the chart display speed, allowing the data to be dis-
played and stored at the rates that best suit the application.
• Language Support - standard language prompts for English UK & US, French, German,
Italian, Spanish, Brazilian, Polish, Hungarian, Slovakian, Czech, Turkish, Romanian, Rus-
sian, Portuguese and Greek.
• Logarithmic Scales - all displayed scales can be set as linear or logarithmic.
decades
• Enclosure rating - standard NEMA 3 / IP54 type front face protection. NEMA 4X / IP66
available as an option.
• Fuzzy Logging - this standard feature provides a unique method to increase the storage
capacity of the recorder. The data is monitored to determine changes in process data; if no
changes are observed data is logged periodically. If data is changing rapidly, it is recorded
normally at the programmed rate. By not logging data that is static, data compression of up
to 100:1 or more can be achieved saving valuable memory.
• Security tag - "wire seal provision" provides added security to seal the front door and rear
when using optional rear cover to prevent undetected entry to these areas of the recorder.
• USB Ports - Front and rear USB host ports for data and setup transfers or remote screen
through these ports. Attach external devices (keyboard or mouse). (Rear USB is an option
for the SIREC D200 recorder, USB 1.1 only).
• Replay with Zoom - Select replay mode and zoom-in on a specific area on the screen. The
data can easily be replayed at the recorder with the ability to "zoom". The touch screen
makes it fast to review and analyse historical data. A "Jump" function allows you to go from
the alarm list directly to the trend showing the occurrence of the alarm.
max 99
43-TV-25-35 GLO Iss.4 Dec 06 UK
A5E01001767-04

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sirec d300Sirec d400

Table of Contents