When the configuration is complete select the Finish button to Commit, Discard or Commit
Later. Select the Back button to return to the previous menu.
If the recorder is set to Active, select Passive and Commit the change. Then return to the
menu and select Active and Commit the change.
(Not available for the SIREC D200 recorder).
(Main Menu > Configure > Setup > Edit Setup> Field IO > Analogue Out)
Only available when an Analogue Out card is fitted as an option, 2 or 4 outputs are available
per card.
Refer to connection details and
Press the Analogue Out button to display all the analogue outputs available. Click on indi-
vidual Analogue Out number to set up each channel profile.
When the configuration is complete select the Finish button to Commit, Discard or Commit
Later. Select the Back button to return to the previous menu.
43-TV-25-35 GLO Iss.4 Dec 06 UK
A5E01001767-04
*Thermocouple Wiring Changes.
Analogue Out Menu
• Enabled - Toggle On and Off.
• Allow Overrange - Toggle On and Off. Disabled as default, this will allow the output sig-
nal to go overrange to 21mA, if disabled the maximum is 20mA.
• Transmit Pen - Eg. Select a pen to output 4-20 mA loop. This will take the scale value
from the pen it is transmitting and convert to 4-20mA output signal. eg if the scale is 0-
50% this signal will fit the scale so 4mA = 0% and 20mA = 50%. For 0-20mA output sig-
nal with the same 0-50% scale, this would read 0mA = 0% and 20mA = 50%.
• Output - Select either 4-20mA or 0-20mA.
• Label - Select and enter an identification label. Select and use the on-screen keyboard.
Up to 16 characters.
Power up
"Analogue Output Channel Numbers" on page 22
Menu path to current menu
The Analogue Out screen
displays all the available
Analogue Output channels.
Each channel displays its
individual settings.
Select a numbered channel
to edit the configuration of
each output
55