Page 2
This page left intentionally blank 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 2/29 ABB Modifications reserved...
Page 3
A terminal to which or from which a direct current or voltage (DC) may be applied or supplied Battery ON: The principal power switch is in the “ON” position OFF: The principal power switch is in the “OFF” position Overload indication Alarm silence Recycle Do not dispose with ordinary trash 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 3/29 ABB Modifications reserved...
2011/65/EU Restriction of the use of certain hazardous substances (RoHS) DIRECTIVE The supplier’s responsibility is excluded in the event of any modification or intervention in the product by the customer’s side. Product Standards Standards RoHS IEC/EN50581:2012 IEC/EN50581:2012 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 6/29 ABB Modifications reserved...
Before carrying out any kind of service and/or maintenance, disconnect the batteries. Verify that no current is present and no hazardous voltage exists in the capacitor or BUS capacitor terminals. Batteries must be replaced only by qualified personnel. 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 7/29 ABB Modifications reserved...
Page 8
Replace the fuse only by a fuse of the same type and of the same amperage in order to avoid fire hazards. Do not dispose the batteries on fire as they may explode. Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 8/29 ABB Modifications reserved...
The battery maintenance shall be done by an authorized Service Partner. Batteries contain dangerous substances that will harm the environment if thrown away. If you change the batteries yourself, call qualified organizations for battery disposal and recycling. 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 9/29 ABB Modifications reserved...
- Leave 25 cm of space on each side of the cabinet to enable cooling airflow and to ensure that the circulation of air to the ventilation slits is not obstructed. - Avoid excessively high temperature and excessive moisture. General Characteristics 3.3.1 Front View 1kVA 2-3 kVA Figure 1: Front View 1-3kVA 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 10/29 ABB Modifications reserved...
3.3.2 Back View UPS with internal batteries UPS without internal batteries Figure 2: Back View of 1kVA UPS with internal batteries UPS without internal batteries Figure 4: Back View of 2kVA 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 11/29 ABB Modifications reserved...
UPS and will provide additional protection to the UPS in the event of overloads and short circuits. Choose the breaker according to the voltage and current indicated in Table 2. UPS Input Breaker Model Voltage Current 1kVA 300Vac 2kVA 300Vac 3kVA 300Vac 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 12/29 ABB Modifications reserved...
The EPO connector is normally opened when the connector is not wired. If the connector is closed with a wire / jumper, the UPS output will not supply energy to the load until the EPO status is again modified. Disable the EPO status Enable the EPO status 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 13/29 ABB Modifications reserved...
DISCONNECTED OR THE BYPASS SWITCH IS ON “OFF” POSITION. For the dimensioning of the DC breaker, consider the voltages and currents indicated in Table 4. DC breaker Model No. Voltage Current 1KVA 48Vdc 2KVA 125Vdc 3KVA 125Vdc Table 4 : DC breaker 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 14/29 ABB Modifications reserved...
Disconnect the utility power to remove the power from the output. From Battery Mode Press OFF button continuously for more than 1 second to turn off the UPS. Power will be then absent in the output of the UPS. 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 15/29 ABB Modifications reserved...
Whenever the batteries are low, the alarm sounds to indicate that the load will be disconnected. In bypass mode, press OFF button continuously for more than 1 second to silence the alarms. This action does not affect the warning and alarms. 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 16/29 ABB Modifications reserved...
UPS will shut down when the OFF key is selected. ON / Silence Alarm Turns on the UPS System, deactivates acoustic alarms in battery mode and performs the battery test (in online mode, ECO mode or converter mode). 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 17/29 ABB Modifications reserved...
“UPS” means the setting of normal inverter mode (Line mode). “ECO” means the setting of economy mode. “CVF” means the setting of converter mode. The detail illustration of the three modes and the operation of the setting are presented in the following section. 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 18/29 ABB Modifications reserved...
Page 19
Note that there is a 10% de-rating when this voltage is set to 208Vac. The user can select one of two frequency values for the output (50 or 60z). The user can enable or disable the bypass of the UPS. 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 19/29 ABB Modifications reserved...
In this mode, the UPS is under alarming situation and can only be shut down after changing the status of the EPO switch in the rear of the UPS. Figure 5: LCD display for UPS with output off 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 20/29 ABB Modifications reserved...
The LCD display of a UPS in online mode is shown in Figure 7. The information on the mains, battery, UPS output and load will be displayed and the word “LINE” and the code “2” will indicate the working mode of the UPS. Figure 7: LCD display for UPS in online mode 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 21/29 ABB Modifications reserved...
Figure 8: LCD display for UPS in battery mode Battery Test – Code 4 4.2.5 The display of the UPS in battery test mode is similar to the one of the battery mode. The battery test mode code is “4”. 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 22/29 ABB Modifications reserved...
“ON” key must be pressed in order to activate the unit with the new parameters. Note that if a confirmation is not given after 30 seconds, the selection mode is de-activated and the dot cursor disappears. 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 23/29 ABB Modifications reserved...
- Go to the website http://www.ups-software-download.com/ - Choose your operating system and follow the instructions described in the website to download the software. - When downloading the files from the internet, enter the serial No: 511C1-01220-0100-478DF2A. 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 25/29 ABB Modifications reserved...
Battery open Overload EPO Active Table 8: Code of the different Warning Fault Code Bus fault Inverter fault Overload fault Over temperature fault Inverter short Bus short Table 9: Code of the different Fault 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 26/29 ABB Modifications reserved...
Page 27
UPS and loads is short circuit. Make sure the short circuit is removed, and the UPS has no internal faults before turning on again. Bus short UPS internal fault Notify dealer Table 10: Troubleshooting table 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 27/29 ABB Modifications reserved...
Page 28
4. Utility power condition, load type and capacity, environment temperature, ventilation condition 5. The information (battery capacity, quantity) of external battery pack if the UPS (if existent) 6. Other information for complete description of the problem 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 28/29 ABB Modifications reserved...
- De-rating to 80% when the output voltage is adjusted to 200VAC - De-rating to 60% when the UPS is in converter mode - Over 1000 m the power de-rating is 1% every 100 m 04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 29/29 ABB Modifications reserved...