U S E R M A N UA L
PowerValue 11 RT G2
1-3 kVA

Advertisement

Table of Contents
loading

Summary of Contents for ABB PowerValue 11 RT G2

  • Page 1 — U S E R M A N UA L PowerValue 11 RT G2 1-3 kVA...
  • Page 2 A B B U P S P R O D U C T S A N D S O L U T I O N S — About this manual — Document information File name 4NWD005357_ABB_OPM_PVA11 1-3kVA-RT_G2_EN_REV-A UPS model PowerValue 11 RT G2 1-3 kVA Date of issue 27.02.2020 Issued by Product Marketing Checked by R&D Article number...
  • Page 3: Table Of Contents

    3.2.5 PowerValue 11 RT G2 3kVA S installation ......12 3 .3 General characteristics .
  • Page 4: Important Safety Instructions

    CABINET: DANGER OF ELECTRICAL SHOCK. DANGER accidental load loss. HIGH FAULT CURRENTS (LEAKAGE CURRENTS). BEFORE CONNECTING THE ABB DOES NOT TAKE ANY RESPONSIBILITY FOR MAINS ENSURE THAT THE UPS IS EARTHED! DAMAGES CAUSED THROUGH INCORRECT USE DANGER DISPLAY A WARNING LABEL ON ALL OF THE UPS SYSTEM .
  • Page 5: Declaration Of Safety Conformity And Ce Marking

    1 I M P O R TA N T S A F E T Y I N S T R U C T I O N S — 1 .3 Declaration of safety conformity and CE marking The PowerValue 11 RT G2 1-3 kVA is designed, These products also meet the following manufactured and commercialized in accordance...
  • Page 6: Maintenance

    DANGER DANGER CAPACITOR OR BUS CAPACITOR TERMINALS. THE BATTERY CIRCUIT IS NOT ISOLATED PowerValue 11 RT G2 1-3 kVA UPS requires only FROM THE INPUT VOLTAGE. HAZARDOUS minimal maintenance. VOLTAGES MAY OCCUR BETWEEN THE BATTERY TERMINALS AND THE GROUND. VERIFY THAT NO VOLTAGE IS PRESENT...
  • Page 7: Ups Disposal And Recycling

    2 M A I N T E N A N C E — 2 .1 UPS disposal and recycling 2 .1 .1 For professional users in the European Union 2 .1 .2 For disposal in countries outside of the European Union THE CROSSED –OUT WHEELED BIN SYMBOL ON THE PRODUCT(S) AND / OR THE CROSSED –OUT WHEELED BIN...
  • Page 8: Installation

    In this case, please and check the following items are included: contact your dealer. • 1 x PowerValue 11 RT G2 UPS • 1 X USB with complete documentation in 5 languages • Multi-language quick installation guide •...
  • Page 9: Site Planning And Positioning

    MAINS SOCKET OUTLET THAT SUPPLIES THE UPS SHALL BE INSTALLED NEAR THE UPS AND SHALL BE WARNING EASILY ACCESSIBLE (NOT APPLICABLE FOR POWERVALUE 11 RT G2 3KVA S) — • AFTER REMOVING COVERS OVER BATTERY TERMINAL, STORE THEM SAFELY FOR FUTURE NEED. REMOVE 3.2.1-3:...
  • Page 10 A B B U P S P R O D U C T S A N D S O L U T I O N S — 1. Install the ear bracket onto the unit using the 3.2.3.2-1: UP TO FOUR EXTERNAL BATTERY M4 flathead screws (figure 3.2.1-1).
  • Page 11: Standalone / Tower Installation

    3 I N S TA L L AT I O N — 3 .2 .4 Standalone / tower installation 3.2.4.1-1: Stabilizer bracket for external battery module 3 .2 .4 .2 External battery modules TO AVOID INJURY FROM TRIPPING, PLACE — 1.
  • Page 12: Powervalue 11 Rt G2 3Kva S Installation

    A B B U P S P R O D U C T S A N D S O L U T I O N S 3 .2 .5 PowerValue 11 RT G2 3kVA S installation — 3.2.5-1: Terminal cover hole...
  • Page 13: General Characteristics

    3 I N S TA L L AT I O N — 3 .3 General characteristics 3 .3 .1 UPS front panel — 3.3.1-1: Figure 3.3.1-1 shows the front panel of the UPS. PowerValue 11 RT G2 front panel — 3.3.2-1: PowerValue 11 RT G2 1kVA B/S...
  • Page 14 EPO/Dry SNMP/AS400 3.3.2-4: AC output 16A AC output 10A AC input 16A RS232 contact input port slot PowerValue 11 RT G2 3kVA S rear view — 3.3.2-5: External battery module rear view — EBM connector USB Port Dry contact output port 3.3.2-4...
  • Page 15: Operation

    4 O P E R AT I O N — 4 Operation This chapter describes how the UPS is operated through the LCD. The user can: • Operate the LCD • Start up and shut down the UPS (excluding the commissioning start up) •...
  • Page 16: Lcd

    A B B U P S P R O D U C T S A N D S O L U T I O N S 4 .1 .2 — 4.1.2-1: The LCD shows an overview of the status of the UPS: The default LCD Battery - Input...
  • Page 17: Operating Mode

    4 O P E R AT I O N — 4 .2 Operating mode The following table describes the UPS status information: — Table 4: Symbols in operating mode Status LCD Screen Description When the input voltage is within acceptable range, UPS will provide Online mode pure and stable AC power to output.
  • Page 18: Ups Start-Up And Shutdown

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 4 .3 UPS start-up and shutdown 4 .3 .2 UPS shutdown SWITCH OFF THE CONNECTED LOADS To shut down the UPS with mains supply: BEFORE TURNING ON THE UPS.
  • Page 19: Lcd Wordings Index

    4 O P E R AT I O N — 4 .4 LCD wordings index The following table describes the UPS status information: — Table 5: Symbols in operating mode Abbreviation Display content Meaning Enable Disable Escape High loss Low loss Converter Temperature Charger fail...
  • Page 20: Lcd Panel

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 4 .5 LCD panel Rack display Tower display Battery Info UPS Display Info UPS Display Info Battery Info Load Info...
  • Page 21: Lcd Settings

    4 O P E R AT I O N — 4 .6 LCD settings CHANGING UPS SETTINGS MIGHT ADVERSELY IMPACT THE LOAD SUPPLY OR LOAD FUNCTIONALITY. IT IS RECOMMENDED TO DISCONNECT THE LOAD BEFORE PROCEEDING WARNING Press and hold select button for 5 seconds to enter UPS settings mode when UPS is in standby mode or bypass mode.
  • Page 22 A B B U P S P R O D U C T S A N D S O L U T I O N S 03: Output frequency settings Interface Settings Parameter 1: Output frequency setting. You may set the initial frequency on battery mode: 50: output frequency is 50 Hz 60: output frequency is 60 Hz If converter mode is enabled, you may choose from the following output frequency:...
  • Page 23 4 O P E R AT I O N 06: ECO frequency range settings Interface Settings Parameter 1: Set the acceptable high frequency point and low frequency point for ECO mode by pressing Down key or Up key HLS: High loss frequency in ECO mode in parameter 1. The setting range in parameter 1 is from 5% to 10% of the nominal voltage.
  • Page 24 A B B U P S P R O D U C T S A N D S O L U T I O N S 08: Bypass voltage range setting Interface Settings HLS: Bypass high voltage point 245-276: Sets the high voltage point in parameter 1 from 245 Vac to 276 Vac (Default: 264 Vac) LLS: Bypass low voltage point 120-215: Sets the low voltage point in parameter 1 from 120 Vac to 215 Vac...
  • Page 25 Interface Settings Set the total capacity in Ah of an external third party battery pack [no standard ABB External Battery Modules (EBM) are connected] Allowed values are integer in the range 7-999 (Ah). The default value is “20” (Ah). Leave as...
  • Page 26 A B B U P S P R O D U C T S A N D S O L U T I O N S 13: Input dry contact Interface Settings Parameter 1: Set input dry contact DIS: Disable the function (default) TON: UPS Turn On TOF: UPS Turn Off MBS: Maintain Bypass...
  • Page 27 4 O P E R AT I O N 18: DC start enable/disable Interface Settings Parameter 1: Set DC start ENA: DC start enable (default) DIS: DC start disable 19: Ambient temperature warning enable/disable Interface Settings Parameter 1: Set ambient temperature warning ENA: Ambient temperature warning enable (default) DIS: Ambient temperature warning disable 20: Automatic battery test...
  • Page 28 A B B U P S P R O D U C T S A N D S O L U T I O N S 23: Short circuit clearance Interface Settings Parameter 1: Set short-circuit clearance ENA: Short-circuit clearance enable DIS: Shortccircuit clearance disable (default) 24: Output receptacles 1 on/off Interface...
  • Page 29: Lcd Measurement Functions

    4 O P E R AT I O N — 4 .7 LCD measurement functions Use the "Select" — 4.7-1: button to navigate Display measurement the display screen. functions When the UPS starts up, the display is in Select Select the default UPS status summary Output current(A)
  • Page 30: Battery Replacement

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 5 Battery replacement 4. Extract the battery tray from the UPS and — 5-1: replace the batteries.
  • Page 31: Communication

    6 C O M M U N I C AT I O N — 6 Communication A USB and an RS-232 port are available to enable If there is a power failure and a predicted communication between the UPS and a remote shutdown of the UPS due to low battery computer/ station.
  • Page 32: Usb Port

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 6 .2 USB port The UPS can communicate with USB-compliant computers that run power management software.
  • Page 33: Network Management Card (Optional)

    6 C O M M U N I C AT I O N — 6 .4 Network management card (optional) The PowerValue 11 RT G2 1–3 kVA is equipped with To install a network management card: an intelligent slot for optional cards for remote 1.
  • Page 34: Troubleshooting

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 7 Troubleshooting — 7 .1 Fault identification and rectification Alarms and events indicate warnings and notify of errors or potential failures in the system.
  • Page 35 7 T R O U B L E S H O OT I N G Symptom Possible cause Remedy No indication and alarm even though The AC input power is not connected Check if input power cord firmly the mains is normal. well.
  • Page 36 — www.abb.com/ups ups.sales@ch.abb.com © Copyright 2020 ABB. All rights reserved. Specifications subject to change without notice.