U S E R M A N U A L
PowerValue 11 RT G2 IN
1-3 kVA

Advertisement

Table of Contents
loading

Summary of Contents for ABB PowerValue 11 RT G2 IN

  • Page 1 — U S E R M A N U A L PowerValue 11 RT G2 IN 1-3 kVA...
  • Page 3 U S E R M A N U A L — Safety symbols and warnings The following symbols are used in this manual, the list below explains each symbol. This symbol in conjunction with the signal word “DANGER” indicates an imminent electrical hazard.
  • Page 4: Table Of Contents

    POWERVALUE 11 RT G2 IN — 1-3 KVA — Table of contents 1. Important safety instructions Operator precautions Environmental considerations Declaration of safety conformity and CE marking Inquiries Operation 2. Maintenance UPS disposal and recycling 2.1.1 For professional users in the European Union 2.1.2 For disposal in countries outside of the...
  • Page 5 U S E R M A N U A L — Table of contents 3.4.3 Recommended cable sections and fuse ratings 3.4.4 PowerValue 11 RT G2 3kVA installation 3.4.5 UPS socket output connection 4. Operation 18-31 4 .1 Control panel 4.1.1 Selection keys 4.1 .2 LCD...
  • Page 6: Important Safety Instructions

    POWERVALUE 11 RT G2 IN — 1-3 KVA — 1. Important safety instructions Read this important safety instruction chapter before reading the operating manual 1.1 Operator precautions 1.2 Environmental considerations Always follow the precautions and instructions To operate the UPS with optimal efficiency, your described in this manual.
  • Page 7: Declaration Of Safety Conformity And Ce Marking

    1.3 Declaration of safety These products also meet the following product standards: conformity and CE marking The PowerValue 11 RT G2 IN 1-3 kVA is designed, Table 1: Standards manufactured and commercialized in accordance Product standards with the EN ISO 9001 standard relating to quality IEC 61000-4-2 Level 3 management systems.
  • Page 8: Maintenance

    POWERVALUE 11 RT G2 IN — 1-3 KVA — 2. Maintenance WARNING! DANGER! Do not open or mutilate batteries. To prevent risk of electric shock, released electrolyte is harmful to only qualified personnel may the skin and eyes. it may be toxic...
  • Page 9: Ups Disposal And Recycling

    U S E R M A N U A L 2.1 UPS disposal and recycling 2 .1 .1 For professional users in the 2 .1 .2 For disposal in countries outside of European Union the European Union The crossed - out wheeled bin symbol on The crossed - out wheeled bin the product(s) and / or accompanying symbol is only valid in the...
  • Page 10: Installation

    POWERVALUE 11 RT G2 IN — 1-3 KVA — 3. Installation 3 .1 Delivery, transportation, 3 .1 .3 Operation of UPS positioning and storage The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C 3 .1 .1 Receipt of the UPS and visual inspection...
  • Page 11: Site Planning And Positioning

    U S E R M A N U A L 3.2 Site planning and positioning WARNING! Handle the UPS carefully to avoid injury WARNING! from falling object. Refer to the • Make sure the mains supply and the technical data sheet for UPS weights. total load demand are within UPS specifications •...
  • Page 12: Rack-Mount Installation

    POWERVALUE 11 RT G2 IN — 1-3 KVA 3.2.4 Rack-mount installation 3.2.4.2 External battery modules WARNING! WARNING! To avoid injury from falling objects make Do not pile UPS and EBM enclosures, they sure that the rack cabinet can accept the might fall over.
  • Page 13: Standalone / Tower Installation

    U S E R M A N U A L NOTE! NOTE! Please install the 4 screws to See technical specifications for ensure that the unit is correctly recommendations. placed in standalone/tower position 3.2.5 Standalone / tower installation 3.2.5.2 External battery modules 1.
  • Page 14: General Characteristics

    POWERVALUE 11 RT G2 IN — 1-3 KVA 3.3 General characteristics 3.3.1 UPS front panel Figure 3.3.1-1 shows the front panel of the UPS. — 3.3.1-1 PowerValue 11 RT - G2 front panel 3.3.2 UPS rear panel The figures below show the connectors and ports in the UPS and external battery module rear panel.
  • Page 15: Electrical Installation

    U S E R M A N U A L — 3.3.2-4 PowerValue 11 RT G2 - 3kVA B rear view — 3.3.2-5 External battery - module rear view 3.4 Electrical installation 3.4.3 Recommended cable sections and fuse ratings When selecting the cable cross-sections and the 3.4.1 UPS input/output connection protective devices, follow the recommendations If the UPS input is connected with power cord,...
  • Page 16 POWERVALUE 11 RT G2 IN — 1-3 KVA 5. Connect three wires according to the WARNING! polarities indicated on the terminal blocks. Be sure to connect ground first. The wiring installation shall be performed by qualified personnel only. 6. Put the terminal cover back on the UPS by fixing 4 screws.
  • Page 17: Ups Socket Output Connection

    U S E R M A N U A L 10. Pass the output cable through the gland 12. Put the terminal cover back on the UPS by assembly; use PVC single cord, 3G, 2.5 mm2, fixing 4 screws. double-insulated, rated 300 V (IEC 60227-1). The overall diameter of the power supply cord must be approximately 10.5 mm to allow reliable clamping from cable gland, to prevent...
  • Page 18: Operation

    POWERVALUE 11 RT G2 IN — 1-3 KVA — 4. Operation This chapter describes how the UPS is operated through the LCD. The user can: • Operate the LCD • Start up and shut down the UPS (excluding the commissioning start up) •...
  • Page 19 U S E R M A N U A L 4.1 .2 LCD The LCD shows an overview of the status of the When powering on, the LCD shows the UPS UPS: status. The UPS will also return to this default •...
  • Page 20: Operating Mode

    POWERVALUE 11 RT G2 IN — 1-3 KVA 4 .2 Operating mode The following table describes the UPS status information: Table 4: Symbols in operating mode Status LCD Screen Description When the input voltage is within acceptable range, UPS will provide Online mode pure and stable AC power to output.
  • Page 21: Ups Start-Up And Shutdown

    U S E R M A N U A L 4. If the bypass has been disabled via the Settings 4.3 UPS start-up and shutdown menu, keep the power button pressed for longer NOTE! than 3 seconds to shut down the UPS. The unit will transfer from online to standby mode.
  • Page 22: Lcd Panel

    POWERVALUE 11 RT G2 IN — 1-3 KVA 4.5 LCD panel Table 6: Symbols in operating mode Display Function Indicates the remaining backup time in pie chart. Indicates the remaining backup time in numbers. H: hours, M: minutes, S: seconds Indicates warning and fault.
  • Page 23: Lcd Settings

    U S E R M A N U A L 4.6 LCD settings WARNING! Changing UPS settings might adversely impact the load supply or load functionality. It is recommended to disconnect the load before proceeding. Press and hold select button for 5 seconds to enter UPS settings mode when UPS is in standby mode or bypass mode.
  • Page 24 POWERVALUE 11 RT G2 IN — 1-3 KVA 03: Output frequency settings Interface Settings Set up output frequency. You may set the initial frequency on battery mode: 50: output frequency is 50 Hz 60: output frequency is 60 Hz If converter mode is enabled, you may choose from the following output frequency:...
  • Page 25 U S E R M A N U A L 06: ECO frequency range settings Interface Settings Set the acceptable high frequency point and low frequency point for ECO mode by pressing Down key or Up key HLS: High loss frequency in ECO mode. The setting range in parameter 2 is from 5% to 10% of the nominal voltage.
  • Page 26 POWERVALUE 11 RT G2 IN — 1-3 KVA 08: Bypass voltage range setting Interface Settings Set the acceptable high voltage point and low voltage point for Bypass mode by pressing the Down key or Up key HLS: Bypass high voltage point...
  • Page 27 U S E R M A N U A L LLS: Bypass low frequency point 46.0-49.0: Sets the low frequency point in parameter 2 from 46.0 Hz to 49.0 Hz for 50 Hz system. (Default: 46.0 Hz) 56.0-59.0: Sets the low frequency point in parameter 2 from 56.0 Hz to 59.0 Hz for 60 Hz system.
  • Page 28 Interface Settings Set up total capacity in Ah of an external third party battery pack [no standard ABB External Battery Modules (EBM) are connected]. Allowed values are integer in the range of 7-999 (Ah). The default value is “20” (Ah).
  • Page 29 U S E R M A N U A L 17: EPO logic setting Interface Settings Set up the EPO function control logic. AO: Active Open (Default). When AO is selected as EPO logic, it will activate EPO function with Pin 1 and Pin 2 in open status. AC: Active Close.
  • Page 30 POWERVALUE 11 RT G2 IN — 1-3 KVA 23: Auto Restart enable/disable Interface Settings Enable or disable auto restart function. ENA: Auto restart enable (default) DIS: Auto restart disable 24: Automatic overload restart enable/disable Interface Settings Enable or disable automatic overload restart.
  • Page 31: Lcd Measurement Functions

    U S E R M A N U A L 4.7 LCD measurement functions Use the "Select" button to navigate the display screen. When the UPS starts up, the display is in Select Select the default UPS status summary Output current(A) Negative bus voltage(V) screen.
  • Page 32: Battery Replacement

    POWERVALUE 11 RT G2 IN — 1-3 KVA — 5. Battery replacement 5. Reinsert the battery tray with the replaced WARNING! batteries back into the original location Please refer to chapter 2 for safety instructions. Please read the following instructions to perform a correct battery replacement: 1.
  • Page 33: Communication

    U S E R M A N U A L — 6. Communication A USB and an RS-232 port are available to enable Table 7: Communication port pin assignment communication between the UPS and a remote Signal Direction Function computer/ station. Only one communication port name from UPS can be active at a time and priority is given to the...
  • Page 34: Dry In

    POWERVALUE 11 RT G2 IN — 1-3 KVA 6.4 Network management card 6.3.1 Dry IN (optional) Dry in allows a remote action to switch on/ switch off/ maintenance bypass the UPS. This is done by The PowerValue 11 RT G2 1–3 kVA is equipped with switching the contact from Opened to close.
  • Page 35: Troubleshooting

    U S E R M A N U A L — 7. Troubleshooting 7.1 Fault identification and rectification Alarms and events indicate warnings and notify errors or potential failures in the system. The output of the UPS is not necessarily affected when an alarm arises but taking the correct actions may prevent loss of power to the load.
  • Page 36 POWERVALUE 11 RT G2 IN — 1-3 KVA Symptom Possible cause Remedy The AC input power is not Check if input power cord is firmly connected well. connected to the mains. No indication and alarm even though the mains is normal.
  • Page 38 — ABB India Helpline Technical telephone support for customers and channel partners. Toll free: (BSNL) +91 1800 420 07 07 abb.com/ups © Copyright 2022 ABB. All rights reserved. Specifications subject to change without notice.