ABB PowerValue 11 RT G2 IN User Manual

ABB PowerValue 11 RT G2 IN User Manual

6-10 kva
Hide thumbs Also See for PowerValue 11 RT G2 IN:

Advertisement

Quick Links

U S E R M A N U A L
PowerValue 11 RT G2 IN
6-10 kVA

Advertisement

Table of Contents
loading

Summary of Contents for ABB PowerValue 11 RT G2 IN

  • Page 1 — U S E R M A N U A L PowerValue 11 RT G2 IN 6-10 kVA...
  • Page 3 U S E R M A N U A L — Safety symbols and warning The following symbols are used in this manual, the list below explains each symbol. This symbol in conjunction with the signal word “DANGER” indicates an imminent electrical hazard.
  • Page 4: Table Of Contents

    POWERVALUE 11 RT G2 IN — 6-10 KVA — Table of contents 1. Important safety instructions Operator precautions Environmental considerations Declaration of safety conformity and CE marking Inquiries Operation Maintenance Installation 10-18 Delivery, transportation, positioning and storage 3.1.1 Receipt of the UPS and visual inspection 3.1.2 Unpacking list...
  • Page 5 U S E R M A N U A L — Table of contents 4. Operation 19-32 Control panel 4.1.1 Selection keys 4.1.2 LED’s status indicators 4.1.3 LCD 4.2 Operating mode 4.3 UPS start-up and shutdown 4.3.1 UPS start-up 4.3.2 UPS shutdown 4.4 Display functions 4.5 LCD operation 4.6 LCD settings...
  • Page 6: Important Safety Instructions

    POWERVALUE 11 RT G2 IN — 6-10 KVA — 1. Important safety instructions Read this important safety instruction chapter before reading the operating manual 1.1 Operator precautions 1.2 Environmental considerations Always follow the precautions and instructions To operate the UPS with optimal efficiency, your described in this manual.
  • Page 7: Declaration Of Safety Conformity And Ce Marking

    These products also meet the following product 1.3 Declaration of safety standards: conformity and CE marking Table 1: Standards The PowerValue 11 RT G2 IN 6-10 kVA is designed, Product standards manufactured and commercialized in accordance Safety IEC/EN 62040-1:2008+A1:2013 with the EN ISO 9001 standard relating to quality IEC/EN 62040-2:2006 management systems.
  • Page 8: Maintenance

    POWERVALUE 11 RT G2 IN — 6-10 KVA — 2. Maintenance PowerValue 11 RT G2 IN 6-10 kVA UPS requires DANGER! only A battery can present a risk of minimal maintenance. electrical shock and high short-circuit current. The following precautions should be observed...
  • Page 9 U S E R M A N U A L 2.1 UPS disposal and recycling 2 .1 .1 For professional users in the 2 .1 .2 For disposal in countries outside of European Union the European Union The crossed - out wheeled bin symbol on The crossed - out wheeled bin the product(s) and / or accompanying symbol is only valid in the...
  • Page 10: Installation

    • 1 x OVCD Box 3.2.2 Positioning • 1 x USB flash driver PowerValue 11 RT G2 IN can be mounted in a rack • 1 x 15-pin communication cable or installed in a standalone configuration. (for parallel systems) •...
  • Page 11: Rack Mount Installation

    U S E R M A N U A L 3 I N S Ta L L aT I O N 3 .2 .3 .2 External battery modules 3 .2 .4 — 04 Battery module 3.2.3 Rack mount installation 3.2.3.2 External battery modules Identify the final position and keep 3U spacing 3 .2 .4 .1 connection...
  • Page 12: Standalone / Tower Installation

    POWERVALUE 11 RT G2 IN — 6-10 KVA A B B U P S P R O D U C T S A N D S O L U T I O N S 3.2.4 Standalone / tower installation 3.2.4.2 External battery modules 3.2.4.1 UPS...
  • Page 13: General Characteristics

    U S E R M A N U A L 3.3 General characteristics 3.3.1 UPS front panel Figure 8 shows the front panel of the UPS. — UPS front panel 3.3.2 UPS rear panel The figures below show the connectors and ports in the UPS and external battery module rear panel. —...
  • Page 14: Electrical Installation

    POWERVALUE 11 RT G2 IN — 6-10 KVA 3.4 Electrical installation Table 4: Recommended cable cross-sections Model 33.4.1 Commissioning Protective earthing 10 mm^2 16 mm^2 conductor The commissioning of the UPS includes the (8 AWG) (6 AWG) (min. cross-section) connection of the UPS and batteries, the...
  • Page 15: Connections

    U S E R M A N U A L 3.4.4 External OVDC box connections 3.4.3 Connections DANGER! WARNING! This Product design for IT system, can’t High leakage current: be used for life support applications Make sure that the earth wire is where failure of this equipment can connected.
  • Page 16: Parallel Installation Operation

    POWERVALUE 11 RT G2 IN — 6-10 KVA Connect UPS and OVDC box as shown in Figure 15. — PDU terminal block access 3.4.5 Parallel installation operation Up to four UPSs can be connected in parallel to configure a sharing and redundant output power.
  • Page 17 U S E R M A N U A L How to install a new parallel UPS system: 1. Before installing a new parallel UPS system, prepare the input/output wires, breakers and a main maintenance mechanical switch or static switch. 2.
  • Page 18 POWERVALUE 11 RT G2 IN — 6-10 KVA 4. Connect the input and output wires and make 7. Switch on the output breakers and main sure all the breakers are turned off. output breaker, transfer the main 5. Turn on the input breakers for the parallel maintenance switch or static switch from UPS.
  • Page 19: Operation

    U S E R M A N U A L — 4. Operation This chapter describes how the UPS is operated through the LCD. The user can: • Operate the LCD • Start up and shut down the UPS (excluding the commissioning start up) •...
  • Page 20 POWERVALUE 11 RT G2 IN — 6-10 KVA 4.1 .2 LCD When powering on, the LCD shows the UPS The LCD shows an overview of the status of the status. The UPS will also return to this default UPS: screen when no buttons have been pressed for •...
  • Page 21: Operating Mode

    U S E R M A N U A L 4 .2 Operating mode The following table describes the UPS status information: Table 4: Symbols in operating mode Status LCD Screen Description When the input voltage is within acceptable range, UPS will provide Online mode pure and stable AC power to output.
  • Page 22: Ups Start-Up And Shutdown

    POWERVALUE 11 RT G2 IN — 6-10 KVA 4.3 UPS start-up and shutdown DANGER! WARNING! Switch off the connected loads The output is still energized. before turning on the UPS. Switch on the loads one by one after the UPS is turned on. Switch off all of the connected loads before turning 3.
  • Page 23 U S E R M A N U A L 4.5 LCD panel Table 6: Symbols in operating mode Display Function Indicates the remaining backup time in pie chart. Indicates the remaining backup time in numbers. H: hours, M: minutes, S: seconds Indicates warning and fault.
  • Page 24: Lcd Settings

    POWERVALUE 11 RT G2 IN — 6-10 KVA 4.6 LCD settings WARNING! Changing UPS settings might adversely impact the load supply or load functionality. It is recommended to disconnect the load before proceeding. Press and hold select button for 5 seconds to enter UPS settings mode when UPS is in standby mode or bypass mode.
  • Page 25 U S E R M A N U A L 04: ECO enable/disable Interface Settings Parameter 1: Output voltage You may choose the following output voltage: 208: presents output voltage is 208Vac 220: presents output voltage is 220Vac 230: presents output voltage is 230Vac (Default) 240: presents output voltage is 240Vac 05: ECO voltage range settings Interface...
  • Page 26 POWERVALUE 11 RT G2 IN — 6-10 KVA 06: ECO frequency range settings Interface Settings Parameter 1: Set the acceptable high frequency point and low frequency point for ECO mode by pressing Down key or Up key HLS: High loss frequency in ECO mode in parameter 1.
  • Page 27 U S E R M A N U A L 08: Bypass voltage range setting Interface Settings Parameter 1: Set the acceptable high voltage point and low voltage point for Bypass mode by pressing the Down key or Up key HLS: Bypass high voltage point 245-276: Sets the high voltage point in parameter 2 from 245 Vac to 276 Vac (Default: 264 Vac)
  • Page 28 POWERVALUE 11 RT G2 IN — 6-10 KVA 09: Bypass frequency range settings Interface Settings Parameter 1: Set the acceptable high frequency point and low voltage point for Bypass mode by pressing the Down key or Up key HLS: Bypass high frequency point 51.0-54.0: Setting the high frequency point in parameter 2 from 51.0 Hz to 54.0 Hz...
  • Page 29 U S E R M A N U A L 11: External battery AH Interface Settings Parameter 1: Set up external battery AH value of the UPS. (unit: AH) 7-999: setting the external battery capacity from 7 to 999. Please set up this figure if external battery modules are connected.
  • Page 30 POWERVALUE 11 RT G2 IN — 6-10 KVA 16: LCD display type Interface Settings Parameter 1: Set LCD display type. RAC: The LCD display type is Rack (Default) TOE: The LCD display type is Tower 17: Audio alarm enable/disable Interface...
  • Page 31 U S E R M A N U A L 22: Automatic overload restart Interface Settings Parameter 1: Set automatic overload restart ENA: Automatic overload restart enable (Default) DIS: Automatic overload restart disable 23: Short-circuit clearance Interface Settings Parameter 1: Set short-circuit clearance ENA: Short-circuit clearance enable DIS: Short-circuit clearance disable (Default) 24: Outlet 1...
  • Page 32: Lcd Measurement Functions

    POWERVALUE 11 RT G2 IN — 6-10 KVA 4.7 LCD measurement functions Use the "Select" button to navigate the display screen. When the UPS starts up, the display is in Select Select the default UPS status summary Output current(A) Negative bus voltage(V) screen.
  • Page 33: Communication

    U S E R M A N U A L — 5. Communication A USB and an RS-232 port are available to enable Table 7: Communication port pin assignment communication between the UPS and a remote Signal Direction Function computer/ station. Only one communication port name from UPS can be active at a time and priority is given to the...
  • Page 34: Dry In

    Dry in allows a remote action to switch on/ switch off/ maintenance bypass the UPS. This is done by The PowerValue 11 RT G2 IN 1–3 kVA is equipped switching the contact from Opened to close. with an intelligent slot for optional cards for remote management of the UPS through the 5.3.2 Dry OUT...
  • Page 35: Troubleshooting

    U S E R M A N U A L — 6. Troubleshooting 6.1 Fault identification and rectification Alarms and events indicate warnings and notify of errors or potential failures in the system. The output of the UPS is not necessarily affected when an alarm arises but taking the correct actions may prevent loss of power to the load 6.2 Accessing alarms...
  • Page 36 POWERVALUE 11 RT G2 IN — 6-10 KVA 6.2.2 Warning indicator Warning Icon (flashing) Alarm Low battery Sounding every second Overload Sounding twice every second Battery is not connected Sounding every second Over charge Sounding every second Over temperature Sounding every second...
  • Page 37 U S E R M A N U A L Symptom Possible cause Remedy The AC input power is not Check if input power cord is firmly connected well. connected to the mains. No indication and alarm even though the mains is normal.
  • Page 38 — ABB India Helpline Technical telephone support for customers and channel partners. Toll free: (BSNL) +91 1800 420 07 07 abb.com/ups © Copyright 2022 ABB. All rights reserved. Specifications subject to change without notice.