    About this manual Symbols The UPS system operates with mains, battery or bypass power. It contains components that carry high currents and voltages. When installed correctly, the UPS system is The following symbols are used in this user manual. grounded to earth and IP 20 rated against electrical shock and foreign objects.
  • Page 4: Table Of Contents

    Contents Safety instructions 1.1 Operator precautions 1.2 Environmental Considerations 1.5 Operation 1.3 Declaration of Safety conformity and CE marking 1.4 Inquiries Maintenance Installation 3.1 Delivery, transportation, positioning and storage 3.2 Site planning and positioning 3.3 General characteristics 3.4 Electrical installation 3.5 Initial startup 3.6 Emergency power off (EPO) 3.7 Paralleling the units...
  • Page 5 4 PowerValue 11 RT 6-10kVA | User manual...
  • Page 6: Safety Instructions

    Under no circumstances install the UPS in an airtight room, in the presence of flammable gases, or in an environment ABB DOES NOT TAKE ANY RESPONSIBILITY FOR DAMAGES exceeding the environmental requirements specified below. CAUSED THROUGH INCORRECT MANIPULATIONS OF THE An ambient temperature of +20°C to +25°C is recommended...
  • Page 7: Operation

    SEE TECHNICAL SPECIFICATIONS FOR Table 1: Standards RECOMMENDATIONS. 1.4 Inquiries INDISCRIMINATE OPERATION OF SWITCHES MAY Address inquiries about the UPS to the local ABB office CAUSE OUTPUT LOSS OR DAMAGE TO EQUIPMENT. or agent authorized by ABB. Note the type code and NOTE the serial number of the equipment before contacting ABB or authorized agent.
  • Page 8: Maintenance

    - WEAR FLAME/ARC RESISTANT WHOLE BODY been exceeded (3~5 years at 25°C ambient temperature). CLOTHING Contact local ABB or an agent authorized by ABB. - WEAR SUITABLE VOLTAGE RATED GLOVES • Charge the UPS once every 4 to 6 months if it has not...
  • Page 9: Installation

    Installation 3.2 Site planning and positioning 3.1 Delivery, transportation, positioning and storage 3.2.1 Planning before the installation Install the unit to a position where any danger to the UPS is 3.1.1 Receipt of the UPS and visual inspection minimized to ensure a long service life: When receiving the UPS, carefully examine the packing •...
  • Page 10 3.2.3 Rack mount installation 3.2.2.1 Connecting the external battery modules Note that you need a rack mounting kit (purchased separately) for this operation. PowerValue 11 RT 6kVA To connect the external battery modules: To install the UPS to a rack: 1.
  • Page 11 PowerValue 11 RT 10kVA 3.2.2.2 Standalone / Tower Installation To connect the external battery modules: 1. Plug the battery module cable into the UPS battery PowerValue 11 RT 6 kVA connector in the rear panel of the UPS as shown in Figure 3.
  • Page 12 PowerValue 11 RT 10 kVA 2. Place the units to a vertical position. 3. Screw the supports to the sides of the unit as shown in To install the UPS in a vertical (tower) position: Figure 7. 1. Carefully rotate the LCD control panel 90º to the right in the top and bottom front panels as shown in Figure 6.
  • Page 13: General Characteristics

    3.3 General characteristics 3.3.1 Front panel Figure 8 shows the front panel of the UPS. On/Off Button Select Button Scroll Button (Up or Back) Scroll Button (Down or Forward) Figure 8: UPS front panel 3.3.2 Rear panel Table 2 and Figures 9, and Table 3 and Figure 10 show the connectors and ports in the UPS rear panel.
  • Page 14 Figure 10: PowerValue 11 RT 10 kVA rear view SNMP/ AS400 slot Parallel port Battery connector GND contact Output sockets Output circuit breaker AC output Bypass AC input Table 3: PowerValue 11 RT 10 kVA rear panel connectors and ports User manual | PowerValue 11 RT 6-10kVA 13...
  • Page 15: Electrical Installation

    UPS and batteries, the verification of the electrical installation and operating environment of the UPS, and the controlled ABB recommends that an external isolating device is installed start-up and testing of the UPS and customer training. between the mains input and UPS as shown in Figure 11 to protect against back-feed currents.
  • Page 16 3.4.3 Connections To access the terminal blocks, remove the 2 screws from the terminal block cover as shown in Figures 12 and 13. Figure 12: PowerValue 11 RT 6 kVA Terminal block Figure 13: PowerValue 11 RT 10 kVA Terminal block User manual | PowerValue 11 RT 6-10kVA 15...
  • Page 17 Single input feed connections In the single input feed configuration, there is a single AC input to the UPS (inverter and bypass). Main low Bypass AC voltage switchboard (MLVS) Load Normal AC Figure 14: UPS diagram with single input feed MAKE SURE THAT THE EARTH WIRE IS CONNECTED.
  • Page 18 Dual input feed connections In the dual input feed configuration, two separate AC inputs are connected to the UPS (one for the inverter and one for the bypass). Bypass AC MLVS1 Load MLVS2 Normal AC Figure 17: UPS Diagram with Dual Input Feed When the Earth system of the inputs are different, a transformer should be connected to the inputs.
  • Page 19 Transformer Bypass AC MLVS1 MLVS2 Load Normal AC Transformer Figure 20: UPS with transformer in normal and bypass inputs MAKE SURE THAT THE EARTH WIRE IS CONNECTED. CAUTION To connect the UPS cables: 1. Ensure that the jumper JP is disconnected. 2.
  • Page 20 Frequency converter connections PowerValue 11 RT can work as a frequency converter, in which case only the input and output should be connected as shown in Figure 23, Figure 24 and Figure 25. Main low voltage switchboard MLVS Load Normal AC Figure 23: UPS diagram as a frequency converter Figure 24: Frequency converter connections for 6kVA units Figure 25: Frequency converter connections for 10kVA units...
  • Page 21: Initial Startup

    3.5 Initial startup 3.6 Emergency power off (EPO) The EPO connector can be used to block the output of the SWITCH OFF THE CONNECTED LOADS BEFORE UPS in case of an emergency. The EPO connector can be TURNING ON THE UPS. SWITCH ON THE LOADS configured as Normally closed (NC) or Normally opened (NO) ONE BY ONE AFTER THE UPS IS TURNED ON.
  • Page 22: Paralleling The Units

    3.7 Paralleling the units Up to 2 UPS units can be connected in parallel with PowerValue 11 RT 6-10 kVA to obtain output power sharing and power redundancy. 3.7.1 Output wiring requirements The following requirements must be met for output wiring: •...
  • Page 23 5. Turn on the mains breakers and the input (I/P) breakers for the two parallel UPS. 6. Keep the power-on button pressed for longer than 1 second in one UPS. The system will start up and go to online-mode. 7. Regulate the output voltage of each UPS separately and check that the output voltage difference between the two UPS units is lower than 0.5V.
  • Page 24 3.7.3 Adding a UPS in parallel to an existing UPS 3.7.4 Removing a single UPS from a parallel system To add a UPS in parallel to an existing UPS: To remove a single UPS from a parallel system: 1. Install a main maintenance mechanical switch or static 1.
  • Page 25: Installation Checklist

    3.8 Installation Checklist • All packing materials and restraints have been removed from all modules. • Each unit in the UPS system is placed in the installed location. • All conduits and cables are properly routed to the UPS and auxiliary cabinets.
  • Page 26: Operation

    Operation This chapter describes how the UPS is operated through the 4.1.1 Selection Keys LCD display. Button Function Illustration The user can: Turn the UPS on and off or change • Operate the LCD display Power on/off operating mode. • Start up and shut down the UPS (excluding the commissioning start up) Enter/exit the menus and scroll across...
  • Page 27: Operating Mode

    4.1.2 LCD display Operating mode Battery information The LCD display shows an overview of the status of the UPS: – Input – Output – Battery UPS output information – load parameters – working mode – settings on voltage – frequency –...
  • Page 28 Status Symbol Description Online-mode UPS is running through the inverter (online-mode) Battery-mode UPS is running on battery. The alarm buzzer sounds every 4 seconds. The power used by the load is supplied from the mains power via an internal filter. Note that if there is a power failure and the UPS in on bypass, it will not transfer back to mains or to Bypass-mode battery-mode.
  • Page 29: Ups Start-Up And Shutdown

    4.3 UPS start-up and shutdown 4.3.2 UPS shutdown To shut down the UPS with mains supply: 1. If the UPS is working on bypass-mode, go to step 3. 2. If the UPS is on online-mode, keep the power-on button pressed for more than 3 seconds. The alarm buzzer will THE FIRST TIME THE UPS IS STARTED UP, IT sound and the UPS will transfer to bypass-mode.
  • Page 30: Display Operation

    4.4 Display operation Figure 32 shows how to navigate through the menus and submenus. Information on the status of the UPS, measurements, events and general information on the UPS are available through the LCD display. This chapter describes how to navigate through the display and how to adjust the user settings.
  • Page 31 4.4.2.3 Control Status: EPO Active Using the Control menu, you can control some features of the Clear EPO status Clear: No UPS. To modify the parameters, press . Then scroll up or down to modify the parameters. To confirm the selection, keep pressed for longer than 1 second.
  • Page 32 1 UPS system Parallel system Turn off single Single UPS turn off: Identification Type/Model: Identification ABB UPS UPS PowerValue 11 RT Single UPS battery Status: battery test ok Settings test Schedule battery test: no Serial Number:...
  • Page 33 If the password is enabled, enter the password USER by pressing the buttons . The password is used mainly to protect against unwanted modifications in the Settings menu. The available operations are listed in Table 8. Submenu item Description Optional Values Default value Language Select menu language...
  • Page 34 Automatic battery tests Bypass frequency high Language period limit <English> <7 days> <+5% (52.5Hz)> ECO mode voltage User password Auto restart low limit <disabled> <enabled> <-5% (218.5.5V)> Automatic overload ECO mode voltage high Audio alarm limit restart <enabled> <+5% (241.5V)> <enabled>...
  • Page 35 34 PowerValue 11 RT 6-10kVA | User manual...
  • Page 36: Communication

    Communication A USB and an RS-232 port are available to enable the communication between the UPS and a remote computer/ station. Only one communication port can be active at a time and the priority is given to the USB port. Once the communication cable is installed, the power management software can exchange information with the UPS.
  • Page 37: Network Management Card (Optional)

    5.3 Network management card To install a network management card: 1. Remove the two screws that protect the communication (Optional) slot of the UPS. PowerValue 11 RT is equipped with an intelligent slot for 2. Insert the SNMP card into the communication slot. optional cards for remote management of the UPS through 3.
  • Page 38: Troubleshooting

    Troubleshooting 6.1 Fault identification and rectification Event log menu From the Event Log menu, you can access the latest 50 Alarms and events indicate warnings and notify of errors or alarms, events and notices, arranged from newest to oldest. potential failures in the system. The output of the UPS is not Events and alarms are logged in the Event Log when they necessarily affected in case of an alarm but taking the correct occur and, if applicable, when they are cleared:...
  • Page 39 Alarm or Event Possible cause Remedy Utility Abnormal The input mains is out of the UPS tolerance range Check input mains condition Alarm Code: 02 Site Fault detection is supported on all-models when Site Fault detection should be enabled by default. It can be Site Wiring Fault a Grounding Neutral connection is present.
  • Page 40 Alarm or Event Possible cause Remedy Ambient Over Temperature Indicates that the ambient temperature is higher than Change the positioning of the UPS or use an adequate air Alarm Code:82 the operation temperature on specification conditioning system. Fan Failure Indicates that the fan is not working properly. Check fans of UPS Alarm Code:84 Back feed...
  • Page 41 40 PowerValue 11 RT 6-10kVA | User manual...
  • Page 42: Appendix A

    Appendix A CS141 SNMP card available parameters (valid for CS141 Basic, CS141 ModBus, CS141 Advanced). The parameters available for CS141 SNMP cards are shown below. Parameter Units Type Available interface Modbus register Measurement Parameters Input Voltage Input Webserver / Modbus Input Frequency Input Webserver / Modbus...
  • Page 43: Appendix B

    Appendix B Winpower SNMP card available parameters (webserver interface) The parameters available from WinPower SNMP cards are shown below. Parameter Type View UPS Status General, status UPS Monitoring >> UPS Status UPS Temperature General, measurement UPS Monitoring >> UPS Status Voltage Input, measurement UPS Monitoring >>...
  • Page 44: Appendix C: External Battery Modules (Ebm) Value Calculation

    Appendix C: External Battery Modules (EBM) value calculation Introduction The battery configuration is described in the following way: “number of battery strings” x ( “number of 12V battery blocks” x “battery capacity”) UPS internal battery configuration UPS Model Battery configuration UPS PowerValue 11 RT 6 kVA no internal UPS PowerValue 11 RT 10 kVA...
  • Page 45 Contact us www.abb.com/ups © Copyright ABB. All rights reserved. Specification subjects to change without notice. ups.sales@ch.abb.com...