Page 1
— U S E R M A N U A L PowerValue 11T IN 6-10 kVA...
Page 3
U S E R M A N U A L — Safety symbols and warnings This symbol in conjunction with the signal word “DANGER” indicates an imminent electrical hazard. Failure to observe the related safety note may cause injury, death or equipment damage. This symbol in conjunction with the signal word “WARNING”...
POWERVALUE 11T IN — 6-10 KVA — Table of contents 1. Important safety instructions Operator precautions Environmental considerations Declaration of safety conformity and CE marking Inquiries Installation Connection warnings Operation 2. Maintenance 9-10 UPS disposal and recycling 2.1.1 For professional users in the European Union 2.1.2 For disposal in countries outside...
Page 5
U S E R M A N U A L — Table of contents 4. Operation 16-25 4 .1 Control panel 4.1.1 Selection keys 4.1.2 LCD 4 .2 Operating mode 4.3 UPS operation 4 .4 LCD wordings index 4.5 LCD panel 4.6 LCD settings 5.
POWERVALUE 11T IN — 6-10 KVA — 1. Important safety instructions Read this important safety instruction chapter before reading the operating manual 1.1 Operator precautions 1.2 Environmental considerations Always follow the precautions and instructions To operate the UPS with optimal efficiency, your described in this manual.
1.4 Inquiries wiring installation. Inquiries regarding the UPS should be addressed to the local ABB office or agent WARNING! authorized by ABB. Note the type code and An integral single emergency the serial number of the equipment before switching device which prevents contacting ABB or authorized agent.
POWERVALUE 11T IN — 6-10 KVA 1.6 Connection warnings 1.7 Operation • There is no standard back feed protection WARNING! inside, please isolate the UPS before working Do not disconnect the mains cable according to this circuit. The isolation device from the UPS or the building wiring must be able to carry the UPS input current.
(around three to five years at 25 °C ambient temperature). Contact DANGER! your local ABB or an agent authorized by ABB A battery can present a risk of electrical shock and high short-circuit for replacements.
POWERVALUE 11T IN — 6-10 KVA 2.1 UPS disposal and recycling 2 .1 .1 For professional users in the 2 .1 .2 For disposal in countries outside of European Union the European Union The crossed - out wheeled bin symbol on...
U S E R M A N U A L — 3. Installation 3 .1 Delivery, transportation, 3 .1 .3 Operation of UPS positioning and storage The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C 3 .1 .1 Receipt of the UPS and visual inspection ambient temperature) has been exceeded, the When receiving the UPS, carefully examine the...
POWERVALUE 11T IN — 6-10 KVA 3 .2 General characteristics 3 .2 .1 Front panel Figure 3.3.1-1 shows the front panel of the UPS. PowerValue 11T PowerValue 11T PowerValue 11T 6KL/10KL 6K/10K 6K/10K — — 3.2.1-1: 3.2.1-2: PowerValue 11T - UPS front panel...
U S E R M A N U A L 3.3.2 Rear panel The figures below show the connectors and ports in the UPS and external battery module rear panel. — — 3.2.2-1 3.2.2-2 PowerValue 11T - 6kVA/10kVA rear view PowerValue 11T - 6kVA/10kVA rear view —...
POWERVALUE 11T IN — 6-10 KVA 3 .3 Single UPS installation 5) Cabinet placement: Secure the UPS to the ground with two shipping brackets A by fixing Installation and wiring must be performed in four screws as shown below chart.
Page 15
U S E R M A N U A L 7) To guarantee wire connection reliability, it is WARNING! necessary to put the cable gland cover back to • For standard battery pack, there the rear panel of the UPS. Keep all cables are one DC breaker to disconnect through the cable gland cover as shown in the battery pack and the UPS.
POWERVALUE 11T IN — 6-10 KVA — 4. Operation This chapter describes how the UPS is operated through the LCD. The user can: • Operate the LCD • Start up and shut down the UPS (excluding the commissioning start up) •...
Page 17
U S E R M A N U A L 4 .1 .2 LCD Table 3: Definition of alarms The LCD shows an overview of the status UPS condition Buzzer status of the UPS: Active fault Continuous • Input Active warning Beep every second •...
POWERVALUE 11T IN — 6-10 KVA 4 .2 Operating mode The following table describes the UPS status information: Table 4: Symbols in operating mode Status LCD Screen Description When the input voltage is within acceptable range, UPS will provide AC mode pure and stable AC power to output.
U S E R M A N U A L 4.3 UPS operation that time, you have to shut down all loads as soon as possible to protect the devices or • Turn on the UPS with utility power supply save data.
POWERVALUE 11T IN — 6-10 KVA 4 .4 LCD wordings index • Mute the buzzer 1) To mute the buzzer, please press the “Mute” The following table describes the UPS button for at least 1s. If you press it again...
U S E R M A N U A L 4.5 LCD panel Table 6: Symbols in operating mode Display Function Indicates the remaining backup time in numbers. H: hours, M: minutes, S: seconds Indicates that the warning and fault occurs Indicates the fault codes, and the codes are listed in details in section 3-9.
POWERVALUE 11T IN — 6-10 KVA 4.6 LCD settings WARNING! Changing ups settings might adversely impact the load supply or load functionality. It is recommended to disconnect the load before proceeding. Press and hold select button for 5 seconds to enter UPS settings mode when UPS is in standby mode or bypass mode.
Page 23
U S E R M A N U A L 03: Voltage range for bypass Interface Settings Parameter 2: Set the acceptable low voltage for bypass. Setting range is from 110V to 209V and the default value is 110V. Parameter 3: Set the acceptable high voltage for bypass. Setting range is from 231V to 276V and the default value is 264V.
Page 24
POWERVALUE 11T IN — 6-10 KVA 09: Battery maximum discharge time setting Interface Settings Parameter 3: 000~999: Set the maximum discharge time from 0 min. to 999 min. UPS will shut down to protect battery after discharge time arrives. The default value is 990 min.
Page 25
U S E R M A N U A L 16: Floating charger voltage adjustment Interface Settings Parameter 2: you may choose Add or Sub to adjust floating charger voltage. Parameter 3: the voltage range is from 0V to 8V, the default value is 0V. 17: Constant charger voltage adjustment Interface Settings...
POWERVALUE 11T IN — 6-10 KVA — 5. Communication A USB and an RS-232 port are available to enable Table 7: Communication port pin assignment communication between the UPS and a remote Signal Direction Function computer/ station. Only one communication port...
U S E R M A N U A L — 6. Troubleshooting 6.1 Fault identification and rectification Alarms and events indicate warnings and notify of errors or potential failures in the system. The output of the UPS is not necessarily affected when an alarm arises but taking the correct actions may prevent loss of power to the load.
POWERVALUE 11T IN — 6-10 KVA 6.2.3 Audible alarm UPS status Buzzer status Muted Bypass mode Beeping once every 2 minutes Battery mode Beeping once every 4 seconds Fault mode Beeping continuously Warning Alarm Muted Overload Beeping twice every second...
U S E R M A N U A L 6.2.4 Troubleshooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Remedy No indication and alarm in the front The AC input power is not Check if input power cord is firmly display panel even though the mains...