UPS USER MANUAL
MegaFlex
1000 to 1600 kW UL S1

Advertisement

Table of Contents
loading

Summary of Contents for ABB MegaFlex UL S1 Series

  • Page 1 — UPS USER MANUAL MegaFlex 1000 to 1600 kW UL S1...
  • Page 2 The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of ABB. The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.
  • Page 3 UPS. Thank you for choosing ABB! Start-up and commissioning! An ABB Global Services Field Engineer must perform start-up and commissioning of the UPS. Please contact ABB Service Center at least two weeks prior to schedule start-up and commissioning at 1-800-292-3739.
  • Page 4 UPS. While every care has been taken to ensure the completeness and accuracy of this manual, ABB assumes no responsibility or liability for any losses or damages resulting from the use of the information contained in this document.
  • Page 5: Table Of Contents

    5/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Table of content Page Safety rules .................................. 6 Safety symbols and warnings .................................... 8 Cyber security ........................................9 Layout ..................................10 Layout MegaFlex 1000 to 1600 ..................................10 Introduction ................................11 Description ................................
  • Page 6: Safety Rules

    This may require additional field marking or labelling defining appropriate level of PPE (Personal Protection Equipment) to reduce the risk of Arc-flash related injuries. Contact our ABB Service Center for product specific information. Installation This UPS must be installed and connected only by trained personnel.
  • Page 7 7/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Safety instructions when working with Battery Danger! External Battery must be installed and connected to the UPS by Qualified Service Personnel. Installation Personnel must read this entire section before handling the UPS and Battery. Full voltage and current are always present at the Battery terminals.
  • Page 8: Safety Symbols And Warnings

    8/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 1.1 Safety symbols and warnings Safety warnings The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to the UPS system and the supplied critical loads. The non-observance of the warnings reminding hazardous situations could result in human injury and equipment damages.
  • Page 9: Cyber Security

    ABB Ltd and its affiliates are not liable for damages and/or losses related to such security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 10: Layout

    10/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Layout 2.1 Layout MegaFlex 1000 to 1600 Fig. 2.1-3 Control Panel Fig. 2.1-1 MegaFlex 1000 to 1600 - General view Customer Interface Board Connectivity Rack J35DSP Serial port RS232 (only Service Center) J35µP Serial port RS232 for...
  • Page 11: Introduction

    RPA™ - Redundant Parallel Architecture™ Parallel System ABB provides a unique technology called Redundant Parallel Architecture™ (RPA™) that can parallel Uninterruptible Power Supply (UPS) modules with true redundancy. With RPA™, there is no need for external electronics or switches to control the UPS modules in the parallel system.
  • Page 12: Description

    With Back-feed Protection and compliance to EMC standards the MegaFlex 1000 to 1600 complies to current standards. Reliability can be further increased by paralleling up to six UPS units utilizing ABB’s unique RPA™ technology (Redundant Parallel Architecture). With RPA every UPS is controlled in a true peer-to-peer configuration with redundancy in all critical elements and functions, eliminating all single points of failure.
  • Page 13: Block Diagram And Main Elements

    13/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 4.1 Block diagram and main elements Fig. 4.1-1 Block Diagram MegaFlex 1000 to 1600 The MegaFlex 1000 to 1600 system can be divided into the following main elements: Control System MegaFlex 1000 to 1600 is designed with microprocessor-controlled signal processing circuits.
  • Page 14: Operation Modes

    The selection between the two operation modes “VFI mode and eBoost™ Operation Mode”, or switching between operation modes at required time, can be done through the UPS Control Panel (see Section 6.4 / eBoost). Note! The eBoost™ Operation Mode is available only if enabled at the factory by an ABB Service Technician.
  • Page 15: Utility Failure Operation

    15/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 4.2.3 Utility Failure Operation When the Utility is no longer within acceptable tolerances, the Battery will provide the DC power to the Inverter. The Inverter will maintain continuous AC power to the Load until the Battery Voltage reaches the lower limit of the Inverter operation capability.
  • Page 16: Automatic Bypass

    16/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 4.2.5 Automatic Bypass In normal operation, the Load is supplied by the Inverter. When the control system detects a fault in the Inverter, an overload condition or a short- circuit condition, the Automatic Bypass will transfer the critical Load to the Utility without interruption.
  • Page 17: Rpa Parallel System Operation

    17/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 4.3 RPA Parallel System operation 4.3.1 Introduction to the RPA Parallel System Fig. 4.3.1-1 Block diagram RPA Parallel System operation Two or more equal power Units can be paralleled to increase the output power (Paralleling for Capacity) or to improve the overall reliability of an UPS system (Paralleling for Redundancy).
  • Page 18: Features Of Rpa Parallel System

    18/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 4.3.2 Features of RPA Parallel System MegaFlex 1000 to 1600 RPA Parallel System is designed to provide a complete Redundant Parallel Architecture and is free from common equipment. Not only the Inverters but also the Bypass functions are redundant. When one UPS needs maintenance or service, the Load is powered by the other Units.
  • Page 19: Service And Technical Support

    Fig. 4.4-1 Identification label 4.5 Warranty ABB, operating through its authorized agents, warrants that the standard products will be free of defects in materials and workmanship for a period as per contract specifications. Note! This warranty does not cover failures of the product which result from incorrect installation,...
  • Page 20: Recycling Instructions

    UPS packing materials must be recycled in compliance with all applicable regulations. Recycling at the end of service life! ABB, in compliance with environment protection recommends to the User that the UPS equipment, at the end of its service life, must be recovered conforming to the local applicable regulations.
  • Page 21: Control Panel

    21/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Control Panel 5.1 Control Panel Fig. 5.1-1 Control Panel The Control Panel, positioned on the UPS front door, acts as the UPS user interface. Main features: LCD Touch screen color graphic display. See Chapter 6. •...
  • Page 22: Lcd Screen

    22/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A LCD screen Composed of an LCD color “Touch Screen” which provides the following information to users: Synoptic diagram indicating UPS status. • UPS operating, AC and DC metering information. • History of events (alarms and messages).
  • Page 23: Description Of The Selection Keys

    23/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 6.1.1 Description of the selection keys Fig. 6.1.1-1 LCD screen Shows electric parameters values and statistics of use. MEASURES See Section 6.2. Shows in chronological order, all the events occurred (alarms, messages, EVENTS commands, handling, etc.).
  • Page 24: Description Of The Signaling Leds

    The service key allows the ABB Service Technician to access the list of parameters of the product. The UPS configuration, calibration and the parameter list of the product defines settings of the UPS. The UPS configuration, calibration and the parameter list can be accessed by an ABB Service Technician for the product using dedicated service software.
  • Page 25 Inverter or from Automatic Bypass in case of eBoost™ Operation Mode). When blinking, indicates that a regular maintenance service is needed (SERVICE REQUIRED). May be reset by an ABB Service Technician only. See Section 9 – Maintenance – Service check.
  • Page 26 26/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A LEDs on Synoptic Diagram LED 1 Rectifier LED 2 Inverter LED 3 Booster/Battery charger LED 4 Automatic Bypass LED 5 LOAD Examples of typical scenarios in the Synoptic Diagram: Load supplied by Inverter Load supplied by Automatic Bypass eBoost Operation Mode Load supplied by Battery...
  • Page 27: Measures

    27/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 6.2 Measures MEASURES The MEASURES mode is entered any time the “MEASURES” key is pressed. The LCD screen will indicate a series of screenshots showing the measures of all electric parameters like AC, DC and various statistics.
  • Page 28 28/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Battery screen Voltage The Battery voltage. Current The Battery current (negative values correspond to the discharge of the Battery). Temperature The temperature of the Battery (“XXX” indicates sensor disabled). Autonomy The estimated backup time with the present Load.
  • Page 29 29/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Bypass screen Frequency The frequency of the input Utility. Voltage L12 / Voltage L23 / Voltage L31 3-phase Utility voltage PHASE /PHASE. Current L12 / Current L23 / Current L31 Input Utility current for the 3-phases.
  • Page 30 30/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A LOAD screen Voltage L12 / L23 / L31 Output voltage PHASE/ PHASE for each phase. Current L1 / L2 / L3 The output current as RMS values for each phase. Percent load L1 / L2 / L3 The output Load as percentage for each phase.
  • Page 31: Events

    See Section 6.6. Key to reset general alarm and buzzer. Shows the screen User Events. Shows the screen Service Events. Reserved for the ABB Service Center. Shows the previous 50 events. Shows the previous 5 events. Shows the next 5 events.
  • Page 32 (Nr. 511 is the more recent, Nr. 1 is the first). Data (MM/DD/YYYY). Exact hour of the moment when the event occurred (HH/MM/SS/ thousandth). Number of standard ABB code of the event. Explicit text describing the event in the selected language. Screen Service Log...
  • Page 33: Events (Alarms And Messages)

    Parameters are lost and have been replaced with default 4000 SETUP VALUES LOST values. Please contact your ABB Service Center for intervention. A blocked DSP on the Control board causes this alarm and 4001 REGULATION BOARD FAILURE consequently the shut-down of Rectifier and Inverter and the opening of K3.
  • Page 34 34/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Code Alarm Description Temperature sensor indicates situation overtemperature on the Rectifier bridge. 4105 RECTIFIER OVERTEMPERATURE Only the alarm is given. The Rectifier, when in an Off state, cannot start as long as this condition persists.
  • Page 35 K6 for 10 seconds. 4406 SSM FAILURE After 3 times K6 remains definitively open. Only an ABB Service Technician can reset the alarm. The Utility Bypass Voltage is out of the tolerances (± 10%). 4410 BYPASS UTILITY OUT OF TOLERANCE K6 opens, synchronization with Utility is inhibited and transfer to Utility is blocked.
  • Page 36 Notice to do the Service Maintenance. Detection of Battery overtemperature condition. 4697 BATTERY OVERTEMPERATURE Only an ABB Service Technician can reset the alarm. In case of Utility Failure, with the actual Load, the run time 4698 BATTERY POWER INSUFFICIENT would be below stop operation time (default 3 minutes).
  • Page 37: Messages List

    37/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 6.3.3 Messages list Code Message Description The microprocessor has detected an incorrect operation: Transfers the load on Utility and performs a program reset. 4002 WATCHDOG RESET The Inverter will restart automatically and will supply the load.
  • Page 38 38/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Code Message Description The command to switch OFF the Inverter has been 4362 INVERTER OFF activated by the Control Panel or automatically for alarm presence. Bypass Input Utility is again within tolerance (voltage, 4411 BYPASS UTILITY OK frequency and phase).
  • Page 39 Code Message Description Inverter can be started or shut-down by remote control. Commands source can be chosen depending on the value of parameter (ABB Service only): 4763 REMOTE CONTROL ON 0 = Only local panel 1 = Only Remote Control 2 = Both Inverter cannot be started or shut-down by remote control.
  • Page 40: Setup

    Key to reset general alarm and buzzer. Shows the screen User. Shows the screen Service Full. Reserved for the ABB Service Center, at this level the parameters access is protected by a “Service Code”. Shows the screen Service Full. Reserved for the ABB Service Center, at this level the parameters access is protected by a...
  • Page 41 41/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Printer screen The UPS is capable of communicating to a serial printer, to printout disparate information. Please be sure to have a serial printer with a serial RS232 interface. This is the only printer-interface supported by the UPS.
  • Page 42 42/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A eBoost screen (option) This screen is displayed only when eBoost™ Operation Mode is available (option). Enabled This parameter (values Yes/No) enables or disables the eBoost™ Operation Mode. If the value is “Yes” and the current time is in the interval for the current day, the eBoost™...
  • Page 43 43/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Hours/Day The number of eBoost™ Operation Mode hours per weekday “Monday to Sunday” is displayed in the operation mode parameter window (ceiling value). Note! To avoid undesired eBoost™ Operation Mode, verify: •...
  • Page 44: Commands

    44/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 6.5 Commands COMMANDS The COMMANDS mode is entered any time the “COMMANDS” key is pressed. Allows the user to execute UPS operation commands. In this mode the keys perform the following functions: Shows the main screen MEASURES.
  • Page 45 Rectifier Rectifier ON Rectifier switching ON command. Rectifier RESET Rectifier restore command. Reserved for the ABB Service Center. Led Rectifier status Indicates the Rectifier’s status: ON = lit OFF = turned Off Inverter Inverter ON Inverter switching ON command.
  • Page 46 The “System shutdown reset” must be done only on one unit connected to the Parallel Bus (“Q1 – External UPS Output Circuit Breaker” closed)! Led System shutdown status Shows the “System shutdown” status: ACTIVE / NOT ACTIVE. Booster Only for ABB Service Center.
  • Page 47 47/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Commands 2 screen Allows the user to execute UPS operation commands. Buzzer TEST Acoustical alarm test (acoustical alarm should be always activated). Module shutdown procedure Guides throught the procedures to shutdown a single UPS or an RPA Parallel System unit.
  • Page 48 48/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Commands 3 screen Allows the user to execute UPS operation commands. Q1 status Indicates the “Q1 – External UPS Output Circuit Breaker” status: OPEN. Q1 CONFIRM Command to confirm that the “Q1 – External UPS Output Circuit Breaker”...
  • Page 49: Rpa Parallel System

    49/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 6.6 RPA Parallel System RPA Parallel System (option) The RPA PARALLEL SYSTEM is entered any time the “RPA” key is pressed. This screen is only displayed when the RPA Parallel System is available (option). screen will provide...
  • Page 50 50/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Description of the RPA Parallel System screen’s main elements RECT Rectifier green color = On grey color = Off CHRG / BST Battery Charger / Booster green color = On grey color = Off Inverter green color = On...
  • Page 51 51/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A RPA screen Voltage L12 / L23 / L31 Output voltage PHASE/PHASE for each phase. Current L1 / L2 / L3 The output current as RMS values for each phase. Percent load L1 / L2 / L3 The output Load as percentage for each phase.
  • Page 52: Operation

    MegaFlex 1000 to 1600 requires the introduction of a “START-UP KEY” code to perform the first commissioning. ENTER The "START-UP KEY" code can be introduced by an ABB Service Technician only. The introduction of the "START-UP KEY" code is mandatory to proceed to the first start-up of the UPS.
  • Page 53: Procedures For Single Megaflex 1000 To 1600

    “OK”. Commissioning cannot be continued should one or more tests result to be negative. Please contact in this case your ABB Service Center. At this stage the Electronic Power Supply and Control Panel are switched ON and the Buzzer sounds.
  • Page 54 Without such configuration it is not possible to continue with the commissioning procedure. Warning! The set-up of the UPS configuration parameters must be done only by an ABB Service Technician! The set-up of mistaken values could compromise the integrity and reliability of the UPS! Language This parameter allows the choice of language used to display the information.
  • Page 55 55/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Battery Capacity Ah capacity of the Battery. Recharge Mode Recharge type of the Battery Normal Valve Regulated Lead Acid Battery (VRLA), NiCd without boost-charge and Flooded Lead Acid Battery without boost-charge.
  • Page 56 56/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Close the “Q1 – External UPS Output Circuit Breaker” (Pos. I). • LED ALARM and Acoustical Alarm are activated. Confirm the closure of the “Q1 – External UPS Output Circuit Breaker” (Pos. I). Perform the “Q1 Status CONFIRM”...
  • Page 57: Complete Ups Shut-Down

    57/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 7.1.2 Complete UPS shut-down Note! Follow this procedure only in case the UPS system and the Load must be completely powered- down. If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure.
  • Page 58: Restore To Normal Operation After "System Shutdown" With Load Not Supplied

    58/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 7.1.3 Restore to normal operation after “System shutdown” with Load not supplied Warning! Please check and ensure the conditions of the connected load are safe before proceeding, as this procedure will result in the connection of power to the load circuit(s). Note! Before performing this operation, make sure that the UPS is in the following status: ...
  • Page 59: Restore To Normal Operation After "Epo - Emergency Power Off" With Load Not Supplied

    59/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 7.1.4 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied Warning! Please check and ensure the conditions of the connected load are safe before proceeding, as this procedure will result in the connection of power to the load circuit(s).
  • Page 60: Procedures Single Megaflex 1000 To 1600 Functioning As Frequency Converter

    “OK”. Commissioning cannot be continued should one or more tests result to be negative. Please contact in this case your ABB Service Center. At this stage the Electronic Power Supply and Control Panel are switched ON and the Buzzer sounds.
  • Page 61 Without such configuration it is not possible to continue with the commissioning procedure. Warning! The set-up of the UPS configuration parameters must be done only by an ABB Service Technician! The set-up of mistaken values could compromise the integrity and reliability of the UPS! Language This parameter allows the choice of language used to display the information.
  • Page 62 62/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Battery Capacity Ah capacity of the Battery. Recharge Mode Recharge type of the Battery Normal Valve Regulated Lead Acid Battery (VRLA), NiCd without boost-charge and Flooded Lead Acid Battery without boost-charge.
  • Page 63 63/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Close the “Q1 – External UPS Output Circuit Breaker” (Pos. I). • LED ALARM and Acoustical Alarm are activated. Confirm the closure of the “Q1 – External UPS Output Circuit Breaker” (Pos. I). Perform the “Q1 Status CONFIRM”...
  • Page 64: Complete Shut-Down Of The Megaflex 1000 To 1600 As Frequency Converter

    64/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 7.2.2 Complete shut-down of the MegaFlex 1000 to 1600 as frequency converter Note! Follow this procedure only in case the UPS system and the Load must be completely powered- down. Initial status: Load supplied by Inverter.
  • Page 65: Restore To Normal Operation After "System Shutdown" With Load Not Supplied

    65/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 7.2.3 Restore to normal operation after “System shutdown” with Load not supplied Warning! Please check and ensure the conditions of the connected load are safe before proceeding, as this procedure will result in the connection of power to the load circuit(s). Note! Before performing this operation, make sure that the UPS is in the following status: ...
  • Page 66: Restore To Normal Operation After "Epo - Emergency Power Off" With Load Not Supplied

    66/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 7.2.4 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied Warning! Please check and ensure the conditions of the connected load are safe before proceeding, as this procedure will result in the connection of power to the load circuit(s).
  • Page 67: Procedures For Megaflex 1000 To 1600 Rpa Parallel System

    “OK”. Commissioning cannot be continued should one or more tests result to be negative. Please contact in this case your ABB Service Center. At this stage the Electronic Power Supply and Control Panel are switched ON and the Buzzer sounds.
  • Page 68 Without such configuration it is not possible to continue with the commissioning procedure. Warning! The set-up of the UPS configuration parameters must be done only by an ABB Service Technician! The set-up of mistaken values could compromise the integrity and reliability of the UPS! Language This parameter allows the choice of language used to display the information.
  • Page 69 69/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Battery Capacity Ah capacity of the Battery. Recharge Mode Recharge type of the Battery Normal Valve Regulated Lead Acid Battery (VRLA), NiCd without boost-charge and Flooded Lead Acid Battery without boost-charge.
  • Page 70 70/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Close the “Q1 – External UPS Output Circuit Breaker” (Pos. I) on all Units. • LED ALARM and Acoustical Alarm are activated. Confirm the closure of the “Q1 – External UPS Output Circuit Breaker” (Pos. I) on all Units. Perform the “Q1 Status CONFIRM”...
  • Page 71 71/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Insert the Inverter performing the “Inverter ON” command on first unit. Perform the “Inverter ON” command from the screen: Commands 1 / INVERTER / ON. • Soft-start of the Inverter indicated with blinking LED 2 (Inverter). •...
  • Page 72: Separate A Ups Unit From The Rpa Parallel System (System Redundancy)

    72/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 7.3.2 Separate a UPS unit from the RPA Parallel System (System Redundancy) Note! If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure. The Load is powered by the UPS Redundant RPA Parallel System.
  • Page 73 Synoptic diagram of other units End of Procedure Danger! It will take 5 minutes for the DC capacitors to discharge. Open only the front door, do not open any other part of the UPS. Note! For any further intervention contact your ABB Service Center.
  • Page 74: Reconnect A Ups Unit To Rpa Parallel System

    74/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 7.3.3 Reconnect a UPS unit to RPA Parallel System Note! The Load is still powered by the other units supplying the Parallel Bus. This UPS unit will be powered on and connected to the Parallel Bus in order to share the Load with each other's.
  • Page 75 75/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Note! Ensure the LED 1 (Rectifier) is lit before carrying out this procedure (3). It indicates that the DC-link 1 and DC-link 2 has reached 400Vdc (see screen MEASURES / Rectifier)! Connect the Battery to the Unit to reconnect by closing the “External Battery Breaker”...
  • Page 76: Complete Rpa Parallel System Shut-Down

    76/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 7.3.4 Complete RPA Parallel System shut-down Note! The UPS RPA Parallel System and the Load have to be completely powered down. If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure.
  • Page 77: Restore To Normal Operation After "System Shutdown" With Load Not Supplied

    77/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 7.3.5 Restore to normal operation after “System shutdown” with Load not supplied Warning! Please check and ensure the conditions of the connected load are safe before proceeding, as this procedure will result in the connection of power to the load circuit(s). Note! Before performing this operation, make sure that all units of the RPA Parallel System are in the following status:...
  • Page 78 78/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Note! Ensure the LED 1 (Rectifier) is lit before carrying out this procedure. It indicates that the DC-link 1 and DC-link 2 has reached 400Vdc (see screen MEASURES / Rectifier)! Connect the Battery to all Units by closing the “External Battery Breaker”...
  • Page 79: Restore To Normal Operation After "Epo - Emergency Power Off" With Load Not Supplied

    79/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 7.3.6 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied Warning! Please check and ensure the conditions of the connected load are safe before proceeding, as this procedure will result in the connection of power to the load circuit(s).
  • Page 80 80/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A Note! Ensure the LED 1 (Rectifier) is lit before carrying out this procedure (3). It indicates that the DC-link 1 and DC-link 2 has reached 400Vdc (see screen MEASURES / Rectifier)! Connect the Battery to all Units by closing the “External Battery Breaker”...
  • Page 81: Options

    UPS, providing status monitoring and alarm notification that supports all ABB UPS product lines, anytime, anywhere. iUPSGuard provides current and detailed information about UPS operation, including its configuration, internal alarms and operating conditions over web.
  • Page 82: Maintenance

    9.1.1 Service check If this lamp lights up during normal operation, the Unit has not been serviced for the last 20,000 hours by an ABB Service Technician. Some components of the UPS which need periodic maintenance, if not replaced, could cause a reliability reduction of the supply system.
  • Page 83: Battery

    Battery replacement, may result in thermal damage to the equipment and an increased risk of personnel injury. ABB declines any responsibility for any damage to the system and the surrounding caused by Battery when the Battery maintenance program is provided by other than ABB itself and ABB authorized partners.
  • Page 84: Notes

    84/86 MegaFlex 1000 to 1600 UPS User Manual / REV-A 10 Notes 10.1 Notes Form It is recommended to note in this section Notes, with date and short description all the operations performed on the UPS, as: maintenance, components replacement, abnormal situations, etc. Date Description Done by...
  • Page 86 — ABB Power Protection SA Via Luserte Sud 9 6572 Quartino Switzerland abb.com/ups © Copyright 2020 ABB. All rights reserved Specifications subject to change without notice...