A B B U P S P R O D U C T S A N D S O L U T I O N S — About this manual — Document information File name 4NWP107193R0001_ABB_OPM_PVA11_1-3kVA-RT_G2_UL_EN_REV-A UPS model PowerValue 11 RT G2 1-3 kVA UL Date of issue 30.09.2020 Issued by Product Marketing Checked by R&D After Sales...
Page 4
A B B U P S P R O D U C T S A N D S O L U T I O N S 6 .3 Emergency power off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 6 .4 Network management card (optional) .
CABINET: DANGER OF ELECTRICAL SHOCK! accidental load loss. DANGER HIGH FAULT CURRENTS (LEAKAGE ABB DOES NOT TAKE ANY RESPONSIBILITY FOR CURRENTS). BEFORE CONNECTING THE MAINS ENSURE THAT THE UPS IS EARTHED! DAMAGES CAUSED THROUGH INCORRECT USE DANGER OF THE UPS SYSTEM .
A B B U P S P R O D U C T S A N D S O L U T I O N S — 1 .3 Declaration of safety conformity and UL marking The PowerValue 11 RT G2 1-3 kVA is designed, These products also meet the following manufactured and commercialized in accordance...
1 I M P O R TA N T S A F E T Y I N S T R U C T I O N S — 1 .5 Operation DO NOT DISCONNECT THE MAINS CABLE INDISCRIMINATE OPERATION OF FROM THE UPS OR THE BUILDING WIRING SWITCHES MAY CAUSE OUTPUT LOSS SOCKET DURING OPERATION AS THIS...
A B B U P S P R O D U C T S A N D S O L U T I O N S — 2 Maintenance The PowerValue 11 RT G2 1-3 kVA UPS requires only minimal maintenance. COMPONENTS INSIDE THE UPS ARE...
2 M A I N T E N A N C E — 2 .1 UPS disposal and recycling 2 .1 .1 For professional users in the European Union 2 .1 .2 For disposal in countries outside of the European Union THE CROSSED –OUT WHEELED BIN SYMBOL ON THE PRODUCT(S) AND / OR THE CROSSED –OUT WHEELED BIN...
Step 3. Put the front panel back on the unit. (figure 3.2.1-3) 3 .2 .3 Positioning The PowerValue 11 RT G2 can be mounted in a rack or installed in a stand-alone configuration. WATER CONDENSATION MAY OCCUR IF THE UPS IS UNPACKED IN A VERY LOW TEMPERATURE.
A B B U P S P R O D U C T S A N D S O L U T I O N S 3 .2 .4 Rack mount installation — 4. Turn off the circuit breaker on external 3.2.4.1-1: 3 .2 .4 .1 UPS battery bank.
3 I N S TA L L AT I O N 3 .2 .5 .2 External battery modules 8. Connect internal battery connector, and put — 3.2.4.2-5: the front panel back to the unit. 1. Set up the extension plate as below and install Battery plug connection it on the UPS stabilizer bracket.
A B B U P S P R O D U C T S A N D S O L U T I O N S — 3 .3 General characteristics 3 .3 .1 UPS front panel — 3.3.1-1: Figure 3.3.1-1 shows the front panel of the UPS. UPS front panel —...
The power cord is supplied in the UPS package. PowerValue 11 RT G2 2 kVA 8*NEMA 5-20R • For PowerValue 11 RT G2 3 kVA models: The 6*NEMA 5-20R + 1*NEMA PowerValue 11 RT G2 3 kVA power cord is attached to the UPS.
4 O P E R AT I O N 4 .1 .2 — 4.1.2-1: The LCD shows an overview of the UPS status: The default LCD Battery - Input status Input/Output information - Output - Battery - Load parameters - Working mode - Frequency - Bypass presence.
A B B U P S P R O D U C T S A N D S O L U T I O N S — 4 .2 Operating mode The following table describes the UPS status information: — Table 5: Symbols in operating mode Status LCD Screen...
4 O P E R AT I O N — 4 .3 UPS start-up and shutdown 4 .3 .2 UPS shutdown SWITCH OFF THE CONNECTED LOADS To shut down the UPS with the mains supply: BEFORE TURNING ON THE UPS. SWITCH 1.
4 O P E R AT I O N — 4 .5 LCD Panel Rack Display Tower Display Load Info UPS Display Info Mode Operation Info Battery Info Load Info UPS Display Info Mode Operation Info Battery Info — Table 7: Symbols in operating mode Display Function Indicates the estimated or running autonomy time.
A B B U P S P R O D U C T S A N D S O L U T I O N S — 4 .6 LCD Setting Press and hold the select button for 5 seconds to enter the UPS setting mode when the UPS is in the standby mode or the bypass mode.
Page 23
4 O P E R AT I O N — 04: ECO enable/disable Interface Setting Parameter 2: Enable or disable the ECO function. You may choose the following two options: ENA: ECO mode enable DIS: ECO mode disable (Default) 05: ECO voltage range setting Interface Setting Parameter 2: Set the acceptable high voltage point and low voltage point for the ECO...
Page 24
A B B U P S P R O D U C T S A N D S O L U T I O N S 07: Bypass voltage range setting Interface Setting Parameter 2: Set the acceptable high voltage point and acceptable low voltage point for the Bypass mode by pressing the Down key or the Up key.
Page 25
4 O P E R AT I O N 11: Autonomy limitation setting Interface Setting Parameter 2: Set up the backup time on the battery mode for general outlets. 0-999: setting the backup time in minutes from 0-999 for general outlets on the battery mode.
Page 26
A B B U P S P R O D U C T S A N D S O L U T I O N S 16: Bypass frequency range setting Interface Setting Parameter 2: Allow or disallow the external output isolation transformer connection. ENA: If selected, connecting to an external output isolation transformer is allowed.
4 O P E R AT I O N — 4 .7 LCD measurement functions Use the Select button to navigate the — 4.7-1 display screen. When the UPS starts Display measurement up, the display is in the default UPS functions status summary screen.
6 C O M M U N I C AT I O N — 6 Communication A USB and an RS-232 port are available to enable If there is a power failure and a predicted communication between the UPS and a remote shutdown of the UPS due to low battery computer/ station.
A B B U P S P R O D U C T S A N D S O L U T I O N S — 6 .2 USB port The UPS can communicate with USB-compliant computers that run power management software.
6 C O M M U N I C AT I O N — 6 .4 Network management card (optional) The PowerValue 11 RT G2 1–3 kVA is equipped with To install a network management card: an intelligent slot for optional cards for remote 1.
A B B U P S P R O D U C T S A N D S O L U T I O N S — 7 Troubleshooting — 7 .1 Fault identification and rectification Alarms and events indicate warnings and notify errors or potential failures in the system.
Page 33
7 T R O U B L E S H O OT I N G Symptom Possible cause Remedy No indication or alarm even though The AC input power is not connected Check if the input power cord is the mains is normal. well.