CHAPTER 4 - Start-up and adjustment of the drive
J1/3 RE
Optoinsulated input for torque enabling. To enable, connect to +15V or +24V, referring to
ØSE.
J1/4 SE
Optoinsulated input for speed reference enabling. To enable, connect to +15V or +24V,
referring to ØSE.
J1/5 TE
Optoinsulated configurable input CONF1. To configure, use parameter P10, IN3_CF (see
paragraph 4.2, in the description of parameters window). To enable, connect to +15V or
+24V, referring to ØSE.
J1/6 ØSE
Common terminal to enable. lf using +15V available on the connector terminal (J1/1) for drive
enabling, connect this terminal to ØD (J1/9 or J1/12).
J1/7 +RIF
Positive input of the speed differential stage.
J1/18 -RIF
Negative input of the speed differential stage.
J1/9 ØD
Zero reference of the board; used also as 0V for the output at +15V, J1/1 and for speed
differential input and current analog input.
J1/10 DIGIOP1.
Digital configurable output 0V
selected on the keyboard with parameter P16, DIG_O1 (see paragraph 4.2).
J1/11 DIGIOP2.
Digital configurable output 0V
selected on the keyboard with parameter P17, DIG_O2 (see paragraph 4.2).
J1/12 ØD
Zero reference of the board; used also as 0V for the auxiliary supply +15V, J1/1 and for
speed differential input and current analog input.
J1/13 +10V
Stabilized supply +10V available externally with maximum load 10mA.
J1/14 -10V
Stabilized supply -10V available externally with maximum load 10mA.
J1/15 RIF2
Input for current reference or for torque analog limit. For current reference the input range is
±10V, while for torque limit the range lies between 0V and +10V (for 0V use ØD, J1/9 or
J1/12)
J1/16 SDOK1
Relay contact 1 that indicates regular operation of the drive.
J1/17 SDOK2
Relay contact 2 that indicates regular operation of the drive. The contact is normally closed
type and opens in case of an alarm.
J1/18, J1/19, J1/20
Terminals currently not used.
J1/21 DAC1
Analog configurable output ±10V: this represents an internal variable of the drive. The
configuration can be set on the keyboard with parameter P12, OUT1_A and P13, DA1SHF
(see paragraph 4.2).
J1/22 DAC2
Analog configurable output ±10V: this represents an internal variable of the drive. The
configuration can be set on the keyboard with parameter P14, OUT2_A and P15, DA2SHF
(see par. 4.2).
MANIU04.9607 GB 03/97
+15V (for size 224 0V
÷
+15V (for size 224 0V
÷
+24V); the configuration can be
÷
+24V); the configuration can be
÷
Page 4.7