8 Operation at Use of a PC
8.3 Configuration of the Device
The Measured Value Recorder Intervals and the PQDIF Files
The measured values recorder intervals are defined according to the averaging intervals setting. This will define
the availability of the PQDif files.
Table 8-15
Set
averaging
interval
30 s
1 min
10 min
15 min
30 min
1 h
2 h
172
PQDIF File Interval (measured value recorder)
Recording
duration for
creating a PQDIF
file
1 h
2 h
2 h, 4 h, 6 h, 12 h,
24 h
Time at start of
Start of recording (recorder start option)
recording of a
complete PQDIF file
00:00 h
- start at the next minute limit
01:00 h
- start at the next 10-minute limit
02.00 h
- immediate start
....
- start at the next hour limit
22:00 h
- start next day
23:00 h
00:00 h
02:00 h
04.00 h
....
20:00 h
22:00 h
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018