15.6

Administrative

The following administrative settings are available:

Time synchronization

Communication Ethernet
Communication serial
Modbus slave devices 1 to 8
SICAM subdevices
Device and language
15.6.1
Time Synchronization
Source time synchronization
Time zone offset
Daylight Saving Time switchover
DST offset
Start of DST
End of DST
Additional Parameters if the Source is Ethernet NTP (Modbus TCP and IEC 61850)
Primary NTP server IP Address
Secondary NTP server IP Address
Error indication after
Error indication after
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Parameter
Additional Parameters if Source is Fieldbus
Default Settings
Internal
+00:00
yes
+01:00
March
Last week
Sunday
02:00 AM
October
Last week
Sunday
03:00 AM
192.168.0.254
192.168.0.253
10 min
10 min
15 Operating Parameters
15.6 Administrative
Setting Range
Internal
Ethernet NTP
Fieldbus
-12 to +13 (hours)
(in increments of 0.5 h)
no
yes
0 to + 2 (hours)
(in increments of 0.5 h)
January to December
First week
Second week
Third week
Fourth week
Last week
Sunday to Saturday
0:00 to 23:00 (full hour)
January to December
First week
Second week
Third week
Fourth week
Last week
Sunday to Saturday
0:00 to 23:00 (full hour)
Any
Any
No polling of the NTP server if 0.0.0.0
was entered
2 min to 120 min
2 min to 120 min