13.2
Test Data
Reference Conditions according to IEC 62586-1 for Determining the Test Data
Ambient temperature
Relative humidity
Supply voltage
Phases (3-wire network)
External continuous magnetic fields
DC components V/I
Signal waveform
Frequency
Voltage magnitude
Flicker
Unbalance (all channels)
Harmonic
Interharmonic
13.2.1
Electrical Tests
Standards
Standards:
Insulation Test according to IEC EN 61010-1 and IEC EN 61010-2-030
Inputs/Outputs
Current measurement inputs
Voltage measurement inputs
Supply voltage
Binary outputs
Binary inputs
Ethernet interface
RS485 interface
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
23 °C ± 2 °C
40 % to 60 % RH
V
± 1 %
PS
3
DC field: 40 A/m
AC field: 3 A/m
none
sinus
50 Hz ± 0.5 Hz
60 Hz ± 0.5 Hz
Udin ± 1 %
Pst < 0.1 %
100 % ± 0.5 % of Udin
0 % to 3 % of Udin
0 % to 0.5 % of Udin
IEC EN 61000-6-2
IEC EN 61000-6-4
IEC EN 61010-1
IEC EN 61010-2-030
Insulation
Rated
Voltage
Reinforced
150 V
Reinforced
600 V
300 V
Reinforced
300 V
Reinforced
300 V
Reinforced
300 V
SELV
< 24 V
SELV
< 24 V
13 Technical Data
13.2 Test Data
ISO Test Voltage
Category
AC 2.3 kV
Cat. III
Surge voltage
Cat. III
9.76 kV
Cat. IV
DC 3.125 kV
Cat. III
AC 3.536 kV
Cat. III
AC 3.536 kV
Cat. III
AC 1500 V
-
DC 700 V
-