7.3

Gateway limits (CK)

7.3.1
Limits of the memory (RAM)
use CK1143
type gateway
stationtype CC1143
visible on CK ?
yes
no
7.3.2
Limits of CERLOOP addressing
use second gate-
way of correct
type
number of
stations > 8 ?
yes
no
the configuration of the
gateway is checked
22
Fire & Security Products
Siemens Building Technologies Group
check gateway configuration
CK1142:
Õ suited for CI1142, CC1142 stations
Õ EPROM set: 'CKQ00xxx'
Õ RAM sets: 4x Z3S080 or 2x Z3S070
CK1143:
Õ suited for CI1142, CC1142, CC1143 stations
Õ EPROM set: 'CKW00xxx'
Õ RAM sets: 4x Z3S070 (RAM upgrade necessary on E3H020)
Via one gateway a maximum of 8 C-Bus stations (CI/CC) can be addressed.
If more than 8 C-Bus stations (CC/CI) are present, they must be split up on two gateways.
Also for special applications, more than two gateways can be configured.
Visibilities of C-Bus stations (CC/CI) on gateways, must be set station wise, not area
wise!
Ü The given limits for the station (CI/CC), the control terminal (CT/CI) and the Algo-
Works utility programs have to be checked as well!
e4595e−7
05.2003