Gateway - Siemens Cerberus CS1140 Planning

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

27

Gateway

27.1
Main features
CT11
C-BUS
CC11
I-BUS
CI11
Line–
Fire & Security Products
Siemens Building Technologies Group
Connection C-Bus network Ö DMS / LMS via V28 interface (RS232)
Conversion of C-Bus Ö CERLOOP/CERBAN
For bridging distances of up to 1000m (double V28 modem integrated)
For distances >1000m use FSK/PSK modem
Per C-Bus network are several gateway possible, see chapter 7
Install preferably in the fire detection system control unit cabinet
Can also be autonomously operated with its own power supply
(E3C011 + B2F020 + batteries)
For the loop node CERLOOP, an additional hardware is necessary (K1H021...)
á Check outline quantities according chapter 7.3
CT11
CK11
Control–
module
Detector
CERLOOP/
CERBAN
DMS/LMS
E3H020
K1H021
42/43
K1D...
Note:
Each 'CC'/'CI' control unit must be assigned a DMS location num-
ber (via programming in AlgoWorks)
* any DMS location numbers according to document e4075
E3H020
CERLOOP (V28)
CERBAN (V28)
75
e4595e 27
05.2003