24.3
Detection line "interactive" Ex
1 Stub line
non–Explosion
hazard area
E3M171
Dxx115x
1) for details see documents e1508 and e1204
24.4
Detection line "CBA8000/TS9000"
4 Loop lines
1
2
E3M120
3
4
62
Fire & Security Products
Siemens Building Technologies Group
Number of addresses: max. 32, Õ restrictions for certain types of devices
T branches allowed
D-Bus max. 32 addresses / 70Ω
SB3
DM115x–Ex
Dxx115x
Dxx115x
Number of addresses per line: max. 119
CBA-Bus max. 119 addresses / 30Ω
CBA8000/TS9000
the software can not proof wheter or not
Non–Ex–detectors are in the explosion
hazard area
Explosion hazard area
DOT1151A–Ex
CBA8000/TS9000
CBA8000/TS9000
CBA8000/TS9000
1)
1)
DT1151A–Ex
DF1151-Ex
DT1151A–Ex
DOT1151A–Ex
e4595e 24
05.2003