Detection Line "Interactive - Siemens Cerberus CS1140 Planning

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

24.2

Detection line "interactive"

1 Loop line
DO115x
E3M071
DC1192
24VDC
DO1101–Ex
DT1101–Ex
DF1101–Ex
1) for details see document e1508
2) for details see document e1204
Programmable control output for 1 external response indicator in each detector base
allocated to another ZONE
Ì
Room 101
Room 102
Ò Ò Ò Ò Ò Ò Ò Ò
ZONE 9
Ò Ò Ò Ò Ò Ò Ò Ò
False ceiling
Ò Ò Ò Ò Ò Ò Ò Ò
Ò Ò Ò Ò Ò Ò Ò Ò
Ë
allocated to the detector
Fire & Security Products
Siemens Building Technologies Group
Number of addresses: max. 128, Õ restrictions for certain types of devices
T branches possible everywhere
DT115x
DOT115x
DOTE115x
D-Bus max. 128 addresses / 120Ω
DC1192
24VDC
Ö Ö Ö Ö
SB3
MS716 collective
MS9 collective
DS11 collective
D2401
max. 5 detectors
Ex
2)
ZONE 7
ZONE 5
Room 103
max. 30 detector
DOW1171
DF1191/92
DCW1151
DM115x
DC1192
CB320A
DO115x
OH
HI
DJ1192
OP
SynoLINE300C
allocated to the detector
ZONE (Default)
Ê
Room 104
3 contacts
DC1157
DBZ1197A
1)
DC1154
DOT115x
DO115x
feedback
contact
DOT115x
Stub line
max. 32 detectors
BFST
Means of linking for external response indi-
cators
Ê
Basic programming
AI external is allocated to the logic detector
ZONE
Ù most frequent application variant
(Default)
Ë
synchronous with the detector AI internal
AI extern is allocated to detector in the base
Ù e.g. for detectors in hollow floors or
false ceilings
Ì
allocated to another ZONE
AI external is treated as a control output
Ù can thus be allocated to any logic
ZONE or several ZONES
1)
Ventilation,
airconditioning,
elevator etc.
3 relay
contacts
DC1156
DLO1191
  Â
  Â
DLR11..
  Â
61
e4595e 24
05.2003