Quiescent Current Table - Siemens Cerberus CS1140 Planning

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

33.3

Quiescent current table

Module
B2F020
0
B1F120
B2Q191/B1Q101
33mA
B3Q321
17mA
B3Q440
25mA
B3Q4..
100mA
B3Q560
75mA
B3Q6../565
100mA
B3Q580
20mA
B3Q590/595
18mA
B3R051
40mA
E3C011
20mA
E3G050
10mA
E3G060
25mA
E3G070
25mA
E3G080
35mA
E3G091
0
0
E3G110
E3H020
100mA
E3I020
25mA
E3L020
22mA
E3L030
18mA
E3M060
155mA
115mA
E3M071
70mA
E3M171
E3M080
85mA
210mA
E3M111
E3M120
8,5mA
E3M220
227mA
E3X101
100mA
E3X102/103
120mA
K1D012
25mA
K1D081
50mA
K1D121
50mA
K1D140
25mA
K1H021
50mA
K3G060
6mA
K3R072
40mA
Z3B171
0
E3I040
15mA
K3I050
15mA
K3I090
50mA
K3I110
24mA
1) only valid for device with APMK = 1 / IMK = 1 (multiply value for devices > 1). Example DC1151: 0,5mA x 12 = 6mA
33.4
Available emergency power supply batteries
AX1201
225487
Battery 12V/27Ah
AX1209
462936
Battery 12V/42Ah
AX1210
475570
Battery 12V/15Ah
AX1212
484325
Battery 12V/12Ah
92
Fire & Security Products
Siemens Building Technologies Group
quiescent current when on battery operation (24V)
as basis for individual calculation of emergency power supply
the current for the 5V supply is included in these values
Quiescent current at 24V
DC
LCD backlight 'inactive' (active = + 100mA)
LCD backlight 'inactive' (active = + 120mA)
LCD backlight 'inactive' (active = + 200mA)
all LEDs inactive
all relays inactive
all control lines terminated
control line 'Horn' terminated
all lines terminated
all channels inactive
only active for emergency operation and
alarm
(=120mA + 0,7mA per MS9i element)
(=50mA + 0,5mA per D-Bus device)
(without external 24V load)
with 32 detectors (=50mA without detectors
+ 0,5mA) per D-Bus device
37mA + 6mA per terminated line
(=50mA + 0,31mA per D-Bus device)
(A+ without external 24V load)
+1,3mA for each detector address
247mA with 82kW terminated
control line 'Horn' terminated
control line 'Horn' terminated
without external 24V load
max. 184mA all Rel. activated incl. service LED
(typical)
0
max. 1A
+
5mA
+
10mA
+ 125mA
+ 185mA
+ 230mA
+
80mA
+ 100mA
+
2mA
0
+
11mA
+
23mA
+
34mA
+
25mA
+
9mA
+
15mA
0
0
+ .. mA
+
40mA
1)
0
1)
0
0
1)
+
10mA
1)
0
0
+ 120mA
+
40mA
+
50mA
0
0
0
0
0
+
3mA
+
2mA
0
+
27mA
0
+
0mA
0
+
10mA
+ 0,5mA
capacity based on battery make 'ALARMCOM' (FIAMM)
"
Additional current with alarm condition
only during printing
per activated LED
per activated relay
per activated control line, without
external load
without external load (horns etc.)
without external load (valves, horns, etc.)
per activated channel
per activated channel for emergency
operation
depends from the activated device
without external load (FBF, HM, FSK)
per line in alarm
per line in alarm condition
without external load (horns, etc.)
without external load (horns, etc.)
per relay
per activated LED
per activated relay
per activated relay
or 4mA per activated LED
per activated relay
per input with closed contact
e4595e 33
05.2003