2. General 2.1 Proper use The actuators are intended to be used exclusively for actuating final control elements (valves, vanes, etc.). Do not use these actuators for any other purpose. Otherwise, a hazard of personal injury or of damage to or impairment of the operational reliability of the device may arise.
8. Mounting 8.1 Actuator Check - Is the actuator filled with the appropriate oil type? - Is enough oil in the actuator? - Did you fasten the separately delivered vent screw in the highest bore (depending on the mounting orientation)? 8.2 Mounting Orientation See table 2 for permissible mounting orientations.
9. Electrical Connection 9.1 Wiring Diagram EBN 853 (Standard) Unterverteilung / Sub Distribution Board Netz / Ext. Sicherung / Schirm beidseitig geerdet ext. fuse Mains screen grounded at both ends Sollwert Istwert Meßumformer BA 1 BA 2 BA 3 BE 1 BE 2 BE 3 Setpoint...
The following steps must be performed to switch the actuator to automatic mode (AUT): - Activate digital inputs DI 1, DI 2 and DI 3 via the configuration program. - Make sure that the supply voltage is available on digital input 1 (DI 1). - Activate AUT mode via the configuration program.
9.4 Wiring diagram EBN 853 (field bus communication ) ext. Vorsicherung / external fuse Netz / Bus in Bus out mains Contrac Leistungselektronik / Busabschluß- möglichkeit / Power Electronics bus termination Busanschluß / bus terminals 17 18 19 20 21 22 23 24 U V W Br Br 13 14 17 18 19 20 21 22 23 24...
Setup The basic settings (definition of end positions) can be made via the Local Control Panel (LCP). It is used for adapting the actuator to the operating range and the effective di- rection without a PC. The actuator can be set up and configured completely using the appropriate configuration program.
10.1.3.1 “Setting” mode Set electronics to “setting” mode by pressing both push buttons (3) simultaneously for approx. 5 seconds, until both LEDs (2 + 8) are flashing synchronously at approx. 4Hz. 10.1.3.2 Defining first position (0% or 100%) Move to desired position by pressing one push button (3). (Higher precision in 2nd To accept the position, press push button (10) or (9);...
11. Maintenance Contrac actuators have a robust construction. As a result, they are highly reliable and require only little maintenance. The maintenance intervals depend upon the ef- fective load and are therefore not specified here. The built-in microprocessor evaluates the actual load factors (e.g. torques, temper- atures, etc.) and derives the remaining operating time until the next routine mainte- nance is required.
Page 15
11.3.2 Mounting The toothed gear pair of the position sensor is held in place by a tension spring (3), to ensure backlash-free motion when the direction of rotation is reversed. - set the stop pin to the center position, as shown in Figure 14. - align the sensor and its gears with the actuator;...
12. Troubleshooting This section only describes how to handle hardware errors. Refer to the configura- tion program’s online help for errors related to the software. Error Possible reason Measures to be taken Disconnect the actuator from the valve. If the actuator is working Malfunction of actuator or Valve cannot be moved by properly then, the valve is...
Page 17
Any infringement of the copyright law will be prosecuted. ABB Ltd. ABB Inc. ABB Automation Products GmbH Subject to technical changes Printed in the Fed. Rep. of Germany Salterbeck Trading Estate 125 E.