ABB RTC-F-1.PB Technical Manual

Room temperature controller

Advertisement

Quick Links

1473-1-8574│14.08.2014
Technical Manual
Room temperature controller
RTC-F-1.PB

Advertisement

Table of Contents
loading

Summary of Contents for ABB RTC-F-1.PB

  • Page 1 1473-1-8574│14.08.2014 Technical Manual Room temperature controller RTC-F-1.PB...
  • Page 2: Table Of Contents

    ® ABB-free@home Content Notes on the instruction manual ________________________________________________________ 3 Safety ____________________________________________________________________________ 4 Used symbols ________________________________________________________________________ 4 Intended use _________________________________________________________________________ 5 Improper use _________________________________________________________________________ 5 Target group / qualification of personnel ____________________________________________________ 5 Safety instructions _____________________________________________________________________ 6 Information on protection of the environment ______________________________________________ 7...
  • Page 3: Notes On The Instruction Manual

    ® ABB-free@home Notes on the instruction manual Notes on the instruction manual Please read this manual through carefully and adhere to the information contained therein. This will assist you in preventing damage to persons and property and ensure reliable operation and long service life of the device.
  • Page 4: Safety

    ® ABB-free@home Safety Safety The device has been constructed according to the latest valid regulations governing technology and is operationally reliable. It has been tested and left the factory in a technically safe and reliable state. However, residual hazards remain. Read and adhere to the safety instructions to pre- vent such hazards.
  • Page 5: Intended Use

    ® ABB-free@home Safety Intended use This device is a room temperature controller for decentralized flush-mounted installation. The room temperature controller (with bus coupler) is suitable for the control of conventional heating and cooling systems. The device is intended for the following: »...
  • Page 6: Safety Instructions

    ® ABB-free@home Safety Safety instructions Warning Electric voltage! Risk of death and fire due to electrical voltage of 230 V. Dangerous currents flow through the body when coming into direct or indirect contact with live components. This can result in electric shock, burns or even death.
  • Page 7: Information On Protection Of The Environment

    ® ABB-free@home Information on protection of the environment Information on protection of the environment All packaging materials and devices bear the markings and test seals for proper disposal. The products meet the legal requirements, in particular the laws governing elec-...
  • Page 8: Product Description

    ® ABB-free@home Product description Product description Fig. 1: Product overview [1] Flush-mounted insert [2] Support ring (not included in scope of delivery) [3] Cover frame (not included in scope of delivery) [4] Cover/push-button (not included in scope of delivery) This device is a room temperature controller for decentralized flush-mounted installation.
  • Page 9: Type Overview

    ABB-free@home Product description Type overview Article no. Product name Sensor channels RTC-F-1.PB Room temperature controller Table 1: Overview of types Function overview The following table provides an overview of the possible functions and applications of the device: Icon of the operating surface...
  • Page 10: Technical Data

    ® ABB-free@home Technical data Technical data Main overview Parameters Value Power supply 24 V DC (via bus line) Bus subscribers 1 (12mA) Bus connection terminal: 0.4-0.8 mm Connection Cable type: J-Y(St)Y, 2x2x0.8 mm Wire stripping: 6-7 mm Protection IP20 Ambient temperature -5 °C –...
  • Page 11: Mounting

    ® ABB-free@home Mounting Mounting Planning instructions Note... Planning and application instructions for the system are available in the free@home system manual. They can be downloaded at www.abb.com/freeathome. Safety instructions for mounting Warning - Risk of death due to electrical voltage Dangerous currents flow through the body when coming into di- rect or indirect contact with live components.
  • Page 12: Mounting / Installation

    ® ABB-free@home Mounting Mounting / Installation » Turn the device into the correct installation position. The mark "TOP" must be aligned toward the top. » Turn the support ring into the correct instal- lation position. The mark "TOP" must be aligned toward the top.
  • Page 13 ® ABB-free@home Mounting » In case the cover has not been pre- mounted or if it has been pulled off, attach it to the device insert. Technical Manual 1473-1-8574 │13...
  • Page 14: Commissioning

    ® ABB-free@home Commissioning Commissioning Commissioning is always carried out via the Web-based surface of the System Access Point. The System Access Point establishes the connection between the free@home participants and the smartphone, tablet or PC. It is used to identify and program the participants during commissioning.
  • Page 15 ® ABB-free@home Commissioning 7.1.1 Adding device Fig. 5: Adding device » In the "Add device" bar select the desired application and pull it via drag-and- drop onto the floor plan in the working area. Fig. 6: Allocation A pop-up window opens automatically which lists all the devices suitable for the application selected.
  • Page 16 ® ABB-free@home Commissioning Identification via serial number Room Temperature Controller RTC flushm. Livingr. ABB700000013 Fig. 7 Identification via serial number » Compare the short 3-digit number of the identity label, which should be glued to the device plan, with the numbers in the list and in this way identify the de- vice you are searching for and, if necessary, also the channel.
  • Page 17: Setting Options Per Channel

    ® ABB-free@home Commissioning Setting options per channel General settings and special parameter settings can be made for each channel. The settings are made via the allocation function of the Web- based user interface of the System Access Point. Device selection Fig.
  • Page 18 ® ABB-free@home Commissioning 7.2.1 Settings of the room temperature controller Actuator settings [1] Changing the name [2] Deleting the channel via 'X' Room Temperature Controller [3] Switching of the actuator via the button Room Temperature Controller [4] Setting the ECO temperature reduction in °C - Specifying the value to which the...
  • Page 19: Linking

    ® ABB-free@home Commissioning Linking The room temperature controllers created via the allocation function can now be linked with binary inputs or heating actuators. The linking in the list view is then made via the linking function of the Web-based user interface of the System Access Point.
  • Page 20: Updating Options

    ® ABB-free@home Updating options Updating options A Firmware update is carried out via the Web-based user interface of the System Access Point. Technical Manual 1473-1-8574 │20...
  • Page 21: Operation

    ® ABB-free@home Operation Operation Note... The scope of delivery contains only the electronic insert. It must still be completed with a suitable cover frame and a cover/a push-button. Additional information about the switch ranges is available in the electronic catalogue (www.busch-jaeger-catalogue.com).
  • Page 22 ® ABB-free@home Operation Off mode Application: The is not being used for a longer period of time. Behaviour of the RTC: The display indicates "OFF". The heating valves are closed (frost protection is active). Antifreeze mode Application: Switches on automatically when a window contact has been con- nected and the window is being opened.
  • Page 23: Displays / Messages

    ® ABB-free@home Operation Displays / messages Fig. 12: Displays [1] Controller on / display of set-point temperature [2] Controller Off [3] Heating active [4] Cooling active [5] Frost protection active [6] Eco mode (indication "ECO") [7] Display of comfort mode heating...
  • Page 24: Maintenance

    ® ABB-free@home Maintenance Maintenance The unit is maintenance-free. In case of damage (e.g., during transport or stor- age), do not perform repairs. Once the device is opened, the warranty is void! Access to the device must be guaranteed for operation, testing, inspection, maintenance and repairs (according to DIN VDE 0100-520).
  • Page 25 ® ABB-free@home A member of the ABB Group Note We reserve the right to at all times Busch-Jaeger Elektro GmbH make technical changes as well as PO Box changes to the contents of this 58505 Lüdenscheid document without prior notice.

Table of Contents