Quickstart Guide
 
ABB PLC and drives integration using Modbus RTU
 
 
Starting up ACS355 drives with FMBA­01 Modbus RTU adapter 
Minimum required parameter settings (based on factory default settings) 
Parameter  Description 
98.02 
COMM PROT SEL 
53.02 
EFB STATION ID 
53.03 
EFB BAUD RATE 
53.04 
EFB PARITY 
53.05 
PROFILE 
53.10 
Actual Speed 
53.11 
Actual Value2 
Drive power down and power up for the new fieldbus settings to take effect! 
10.01 
EXT 1 COMMANDS 
11.02 
EXT1/EXT2 SEL 
11.03 
REF1 SELECT 
16.04 
FAULT RESET SEL 
 
Optional parameter settings 
30.18 
COMM FAULT 
FUNC 
30.19 
COMM FAULT TIME  [optional] 
(11.05) 
REF1 MAX 
*) in Par. 99.02 the Application Macro can be set to "AC500 Modbus (10)" then the parameters are automatically 
set as shown. 
Modbus RTU 
Setting 
Applic Macro 
"AC500 
MODBUS" *) 
STD 
STD 
MODBUS 
MODBUS 
[Address] 
19.2 kbit/s 
19.2 kbit/s 
(example) 
8 NONE 1 
8 NONE 1 
(example) 
ABB DRV 
ABB DRV 
FULL 
FULL 
101 
101 
105 
303 
COMM 
COMM 
COMM 
COMM 
COMM 
COMM 
COMM 
COMM 
 
[optional] 
FAULT
Default:. 3s 
[Scale max]   
‐ 15 ‐ 
Comment 
Activates fieldbus module 
Modbus RTU node address of the drive 
Transfer rate of the link. Same baud rate must 
be defined in the Modbus RTU master. 
Parity and stop bits. Same parity and stop bits 
must be defined in the Modbus RTU master. 
Communication profile "ABB Drives" 
Actual speed feedback 
Actual value2 (e.g torque 105) (303 = Status 
Word 1) 
Fieldbus interface as source for start and stop 
Fieldbus interface as source to switch to EXT2  
Fieldbus interface as source for speed 
reference 
Fieldbus interface as source for fault reset 
How the drive reacts to a fieldbus 
communication break. 
Time between communication break detection 
and the selected action. 
Max speed/frequency scaling value (used in 
function block/visualization input 
"SPEED_REF_MAX"). Must be less or equal to 
drive parameter max speed/frequency. 