Starting Up Acs850, Acq810 Drives With Embedded Modbus Rtu - ABB ACS310 Quick Start Manual

Plc and drives integration using modbus rtu
Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

 
Quickstart Guide
 
ABB PLC and drives integration using Modbus RTU
 
 
Starting up ACS850, ACQ810 drives with embedded Modbus RTU 
Minimum required parameter settings (based on factory default settings) 
Parameter  Description 
50.15 
Fb cw used 
58.01 
Protocol ena sel 
58.03 
Node address 
58.04 
Baud rate 
58.05 
Parity 
58.06 
Control profile 
58.10 
Refresh settings 
10.01 
Ext1 start func 
12.01 
EXT1/EXT2 SEL 
21.01 
Speed ref1 sel 
10.10 
Fault reset sel 
 
Optional parameter settings 
58.07 
Comm loss t out 
58.08 
Comm loss mode 
58.09 
Comm loss action 
58.10 
Refresh settings 
(19.01) 
Speed scaling 
Modbus RTU 
Setting 
Comment 
P.02.36 
Selects the address of the fieldbus Control Word in 
use. 
Modbus RTU  Initializes embedded fieldbus communication. 
Drive‐to‐drive link operation (parameter group 
57) is automatically disabled. 
[Address] 
Modbus RTU node address of the drive 
19.2 kbit/s 
Transfer rate of the link. Same baud rate must be 
(example) 
defined in the Modbus RTU master. 
8 none 1 
Parity and stop bits. Same parity and stop bits must 
(example) 
be defined in the Modbus RTU master. 
ABB Classic 
Communication profile "ABB Drives" 
[optional] 
Refreshes the settings of parameters 
58.01...58.09. 
FB 
Fieldbus interface as source for start and stop 
P.02.36 bit 
Fieldbus interface as source to switch to EXT2 
15 
control location 
EFB ref1 
Fieldbus interface as source for speed reference 
P.02.36 bit 8 
Fieldbus interface as source for fault reset 
[optional] 
Defines the timeout limit for the EFB 
communication monitoring. 
None  or  
Enables/disables EFB communication loss 
Any Message 
monitoring and defines the means for resetting 
the counter of the communication loss delay. 
[optional] 
Defines the drive operation after the EFB 
communication loss monitoring awakes. 
[optional] 
Refreshes the settings of parameters 
58.01...58.09. 
[Scale max] 
Max speed/frequency scaling value (used in function 
block/visualization input "SPEED_REF_MAX"). Must 
be less or equal to drive parameter max 
speed/frequency. 
‐ 18 ‐ 
 
 
PLC and drives integration  