Quickstart Guide
 
ABB PLC and drives integration using Modbus RTU
 
 
Starting up ACS880 drives with FSCA­01 Modbus RTU adapter 
Minimum required parameter settings (based on factory default settings) 
 
Parameter  Description 
50.01 
FBA A enable 
51.02 
PROTOCOL/PROFIL
51.03 
STATION ID 
51.04 
BAUD RATE 
51.05 
EFB PARITY 
52.02 
FBA data in2 
53.02 
FBA data out2 
51.27 
FBA par refresh 
19.11 
Ext1/Ext2 selection  Mcw Bit11 
20.01 
Ext 1 commands 
20.02 
Ext1 start trigger  
22.11 
Speed ref1 
selection 
31.11 
Fault reset 
selection 
 
Optional parameter settings 
50.02 
FBA A comm loss 
func 
51.06 
MODBUS TIMEOUT  [optional] 
51.07 
TIMEOUT MODE 
51.27 
FBA PAR REFRESH 
(46.01) 
Speed scaling 
Modbus RTU 
Setting 
Comment 
Enable 
Activates fieldbus module 
ABB Drives 
Communication profile "ABB Drives" 
Classic or 
Enhanced 
[Address] 
Modbus RTU node address of the drive 
19.2 kbit/s 
Transfer rate of the link. Same baud rate must be 
(example) 
defined in the Modbus RTU master. 
8 NONE 1 
Parity and stop bits. Same parity and stop bits 
(example) 
must be defined in the Modbus RTU master. 
Act1 16bit (5) 
Actual speed as Data Word 2 from the drive 
Ref1 16bit (2) 
Speed reference as Data Word 2 to the drive 
Configure 
Updates fieldbus settings (groups 50 to 57) 
Fieldbus interface as source to switch to EXT2 
(06.01) 
control location 
Fieldbus A 
Fieldbus interface as source for start and stop 
Level 
To directly restart after Coast Stop (Off3) 
FB A ref1 
Fieldbus interface as source for speed reference 
P.06.01 bit 7 
Fieldbus interface as source for fault reset 
[optional] 
Defines the drive operation after the 
communication loss monitoring awakes. 
Time between communication break detection 
and the selected action. 1 = 100 ms. 
CONTROL 
How the drive reacts to a fieldbus communication 
WRITE 
break. 
REFRESH 
Updates fieldbus settings (groups 50 to 53) 
[Scale max] 
Max speed/frequency scaling value (used in 
function block/visualization input 
"SPEED_REF_MAX"). Must be less or equal to drive 
parameter max speed/frequency. 
‐ 19 ‐ 
 
 