Quickstart Guide
 
ABB PLC and drives integration using Modbus RTU
 
 
IP configuration of CPU (for Ethernet connection between PC and PLC) 
If the CPU has an Ethernet port and the CPU IP address has not already been configured, follow the steps below. 
De‐activate  the  firewall  of  the  PC,  or  allow  the  connection  if  question  comes  up.  Connect  an  Ethernet  cable 
between PC and PLC (or via a switch). 
Open the IP configuration tool from the "Tools" menu and press the "Scan" button. 
Select actual PLC from the scanned objects (1), make your network settings (2) and press the "Send Configuration" 
button.  This  needs  to  be  done  the  first  time  you  connect  to  the  PLC  even  if  the  IP  address  is  already  correct. 
 
Note! The PLC needs to be in "STOP" mode for IP configuration.  
After the new configuration was sent the PLC will automatically reboot. 