PDU8000 UPS Power Distribution Cabinet
User Manual
Figure 4-14 Alarm
Step 6 Turn the handle to a desired position (I, O, or II).
----End
Button Mode
When the controller is working in the button mode, a user can control the ATS switch using
the I, O, and II buttons on the controller panel. In the button mode, the OMD800 controller
can control the generator.
Do not simultaneously press and hold down the I, II, and O buttons on the controller panel.
Ensure that the interval between two commands is 5s at least. If another command is issued
before the previous one is executed, the protection fuse (F1) under the electric operation
mechanism may be blown.
Step 1 Switch on the circuit breaker of the ATS operation mechanism based on DC-DC Converting
Principle Diagram to power on the ATS operation mechanism.
Step 2 Check whether the 8D controller has alarms. For the alarm viewing method, see
and
Issue 01 (2016-03-04)
After the handle is inserted, the controller automatically switches to the button operation mode. After the
handle is removed, the controller remains in the button operation mode, and the Alarm LED indicator
turns off.
Table
4-1. If an alarm exists, rectify the fault first.