5.6 Mounting a P style pressure transmitter

(266Gxx, 266Axx, 266Hxx, 266Nxx)
The pressure transmitter can be mounted directly on the
manifold.
A mounting bracket for wall or pipe mounting (2" pipe) is also
available as an accessory.
Ideally, the pressure transmitter should be mounted in a
vertical position to prevent subsequent zero shifts.
1/2 - 14 NPT
Figure 17: Model 266H or 266N High overload resistant P-Style transmitter with 1/2-14 NPT male process connection and barrel housing
installed on a 2"pipe with optional bracket (B6 carbon steel or B7 Stainless Steel 316L)
Figure 18: Model 266H or 266N High overload resistant P-Style transmitter with 1/2-14 NPT female process connection and barrel
housing installed on a 2"pipe with optional bracket (B6 carbon steel or B7 Stainless Steel 316L)
91 (3.58)
32 (1.26) width across
ats of exagon
72 (2.83)
91 (3.58)
72 (2.83)
If the transmitter is installed inclined with respect to the
Important.
vertical, the filling liquid exerts hydrostatic pressure on the
measuring diaphragm, resulting in a zero shift. In such an event, the
zero point can be corrected via the zero push-button or via the "set
PV to zero" command. Please refer to the [configuration section] for
further details. For transmitters without diaphragm seals the Vent /
Drain considerations below should be taken into consideration.
113 (4.45)
18 (0.71)
108 (4.25)
49 (1.93)
113 (4.45)
18 (0.71)
108 (4.25)
49 (1.93)
2600T Series Pressure transmitters | OI/266/HART-EN Rev. M 19
5 Mounting
29 (1.14)
18 (0.71)
29 (1.14)
18 (0.71)
32 (1.26) width across
ats of exagon

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents