ABB 266 HART Series Operating Instruction page 63

Pressure transmitters
Hide thumbs Also See for 266 HART Series:
Table of Contents

Advertisement

— Operation related error messages
Error message Tx LCD message Possible cause
Power Supply
M024.036
Warning
Power Supply
M024.036
Warning
Electronic
M022.041
Temperature Out of
Limits
Electronic
M022.041
Temperature Out of
Limits
— Process related error messages.
Error message Tx LCD message Possible cause
F104.032
Pressure Overrange
F102.004
P-dP Out Of Limits
Static Pressure Out
F100.005
of Limits
Sensor Temperature
S054.006
Out of Limits
Max Working
S052.031
Pressure Exceeded
Analog Output
F098.034
Saturated
Analog Output
F098.034
Saturated
M018.038
PILD Output
PILD-Changed Op.
M016.039
Conditions
The Device Power Supply is close to the lowest
acceptable limit.
The Device Power Supply is close to the highest
acceptable limit.
The Electronics temperature is out of its lower
acceptable limit . The circuitry for the sampling of
the Electronics Temperature has failed.
The Electronics temperature is out for its Higher
acceptable limit. The circuitry for the sampling of
the Electronics Temperature has failed.
This effect could be produced by other equipment on the
process, (valves.....). Exceeding the pressure range can
cause reduced accuracy or mechanical damage to the
diaphragm material and may require calibration/replacement.
The measurement range has not been correctly calculated
OR an incorrect transducer model has been selected.
The static pressure of the process exceeds the limit of the
sensor. Exceeding the Static Pressure can reduce accuracy,
mechanically damage the diaphragm and may require
calibration/replacement. An incorrect transducer model
could have been selected.
The temperature of the process environment affects the
pressure transmitter; Excess temperature can reduce
accuracy, degrade device components and may require
calibration/replacement.
The static pressure of the process exceeds the max working
Pressure supported by the transmitter. Exceeding the Max
Working Pressure can mechanically damage the process
connections (flanges, pipes....) and/or be dangerous.
The analog output for the Primary Variable is beyond its Low
scaling limit and no longer represents the true applied
process. The Analog Output (4-20 mA) is saturated to the
configured Saturation Limit Low.
The analog output for the Primary Variable is beyond its High
scaling limit and no longer represents the true applied
process. The Analog Output (4-20 mA) is saturated to the
configured Saturation Limit High.
One (HIGH or LOW) or both connections between the
pressure sensor and the process is blocked either by
plugging or closed valves.
Process conditions have changed to an extent that new
settings for the PILD algorithm are needed.
Suggested action
Check the Voltage at the terminal block and if it is not
within the valid range check the external power
supply.
Check the Voltage at the terminal block and if it is not
within the valid range check the external power
supply.
The Electronics should be replaced as soon as
possible.
The Electronics should be replaced as soon as
possible.
Suggested action
The compatibility of pressure transmitter
model and process conditions has to be
checked. A different transmitter type could
be required.
The compatibility of pressure transmitter
model and process conditions has to be
checked. Probably a different transmitter
type is required.
The compatibility of pressure transmitter
model and process conditions has to be
checked. Probably a different transmitter
type is required.
The compatibility of pressure transmitter
model and process conditions has to be
checked. A different installation type could
be required e.g. use of remote seals.
The compatibility of pressure transmitter
model and process conditions has to be
checked.
Adjust the Saturation Limit or the working
range if possible.
Adjust the Saturation Limit or the working
range if possible.
Check valves and impulse line.
Clean impulse line if necessary and initiate
PILD training.
A new Training is necessary for this new
process condition.
2600T Series Pressure transmitters | OI/266/HART-EN Rev. M 63
9 Error messages
Tx response
no effect
no effect
no effect
no effect
Tx response
no effect
no effect
no effect
no effect
no effect
no effect
no effect
no effect
no effect