8.10 LCD (L1 and LS option) activation
considerations
Gain access to the display by unscrewing the windowed cover.
Please observe the Hazardous area prescription before
proceeding with the cover removal. For activation, see below.

8.11 Through The Glass (TTG) (L5 option) activation

considerations
The TTG technology allows the user to activate the keypad on
HMI without the need of opening the windowed cover of the
transmitter. The capacitive pick-ups detect the presence of a
finger in front of the respective button activating the specific
command. At the transmitter power-on the HMI automatically
calibrate its sensitivity, it is mandatory for proper functioning of
the TTG HMI that the cover is properly tightened at power-on.
In case the cover has been removed to access the
communication board, it is recommended to power off and
power-on again the transmitter once the windowed cover has
been set in place and properly tightened.
Important. Do not operate TTG display (L5 option) for 30 seconds
after transmitter power-on. During this period of time, the
transmitter is calibrating the capacitive switches.

8.12 Activation procedure for LCDs

The LCD displays L1 and L5 selectable for Advanced HART
and Safety HART versions features 4 push buttons (see figure
49) that allow the navigation through the various functions.
— Press simultaneously the buttons (2)
two icons will appear at the bottom corners of the display.
— Press the button (4)
second to access the HMI menu or press the left button
(1)
to access the instantaneous diagnostic messages.
For TTG display, in case of pressing not correct the following
display will appear with "!" marks in the corners.
For Standard HART version, to access to configuration menu
press simoultaneously the Z and S buttons, on-board of LS
display or external under the nameplate, two icons will appear
at the bottom corners of the display. Press then for 2 s. the
right button or external S pushbutton to access the menu or
press the left button or external Z pushbutton to access signals
view or diagnostic messages. Without action on buttons
associated to bottom icons after few seconds the transmitter
return to normal operation displaying letters in the corners.
38 OI/266/HART-EN Rev. M | 2600T Series Pressure transmitters
and (3)
under the right icon within one

8.13 HMI menu structure

Standard HART version features only the Easy Setup menu in a
dedicated structure, different from other HART versions. Once
accessed the menu should be completed until the last step
HART Revision is reached, then to return to the normal display
view. For each step follow the instructions on the screen and
consider that for alfa/numeric parameters it is required to move
digit by digit until the right bottom corner display OK. Pressing
the right on-board button or the external S pushbutton the
operation is confirmed, while pressing the left on-board button
or the external Z pushbutton the display change to CANCEL to
abort the operation by the associated button (right/S).
Important. After 30 seconds without action on on-board buttons or
external Z/S pushbuttons, the Standard HART transmitter
automatically exit the configuration menu.
For Advanced HART and Safety HART versions the HMI menu
is divided in the following sections which can be selected by
acting on the keys (2)
desired sub-menu icon will be visualized, confirm your selection
with the [SELECT] key (4)
Follow the instruction on the screen to perform the
configuration of the different parameters.
until
This menu allows the verification and the parameterization of
the basic configuration of the 266 pressure transmitter. The
menu driven structure will guide you to the choice of the
interface language, the tag number configuration, the
engineering units, the URV and LRV (Upper range value and
lower range value), the transfer function (linear or square root)
the damping time, the auto set zero (set the input measured
value to 4 mA and the PV value to 0), the display visualization
mode (the value that need to be visualized on the LCD).
This menu allows the verification and the parameterization of the
entire device The menu driven structure includes the write
protection enabling, process variable settings (unit, LRV and URV),
transfer function selection (linearization type and low flow) and
output scaling (unit according to the measurement and LRV/URV).
The last selectable sub-menu allows user to reset all the
parameters to the default configuration.