PDU8000 Precision PDC-T
User Manual
Figure 2-4 Not tied at bends
Figure 2-5 Extra length for easy plug and unplug
Figure 2-6 Stroking cables
Cable Layout
Table 2-5 Cable layout rules
No.
1
2
3
Issue 01 (2017-07-15)
Cable Layout Rule
The armoring layers of armored cables are grounded.
The PDC ground cable is secured to the equipment room ground bar. The
resistance between the PDC ground cable and the equipment room ground
bar is less than 0.1 ohm.
Cables are securely connected in the correct phase sequence.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2 Installation Guide
11