PDU8000 Precision PDC-T
User Manual
Figure 5-56 Upgrade Software (5)
Step 6 Tap Activate to activate the software. After the software is activated, the MDU is restarted.
Figure 5-57 Upgrade Software (6)
Issue 01 (2017-07-15)
The MDU is not restarted if the software for the monitoring board is activated and is restarted if the
software for the MDU is activated.
If the PDC is powered off when the software for the monitoring board is being upgraded, the
information about the monitoring board is not displayed after the MDU is restarted. In this case, tap
Upgrade Software to continue the upgrading process. If the PDC is powered off when the software
for the MDU is being upgraded, perform the upgrading again after the MDU is restarted.
After the software is upgraded, the MDU parameters remain unchanged and do not need to be reset.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 MDU Commissioning Guide
58