Huawei PDU8000-0630ACV4-SCA108 User Manual page 45

Precision pdc-t
Table of Contents

Advertisement

PDU8000 Precision PDC-T
User Manual
You can set IP address allocation to Manual or Automatic. If the MDU restarts, IP address allocation
automatically changes to Automatic. The IP address is bound as the IP address set last time, allowing
you to log in for the second time.
Set an IP address for the Ethernet. The value ranges from 0.0.0.0 to 255.255.255.255. The
default value is 192.168.0.10.
Ensure that the IP address is unique on the network segment. Otherwise, the LCD cannot
work properly.
Set a subnet mask for the Ethernet. The value ranges from 0.0.0.0 to 255.255.255.255. The
default value is 255.255.255.0.
Set an Ethernet gateway. The value ranges from 0.0.0.0 to 255.255.255.255. The default value
is 192.168.0.1.
Set the serial port communications rate. The value options include 4800, 9600, and 19200.
The default value is 9600.
Set the serial port communications address. The value ranges from 0 to 254. The default value
is 1.
SNMP Version can be set to ALL, SNMPv1&v2c, or SNMPv3. SNMP Port can be set to a
value in the range from 1 to 65535. The default value is 161.
Issue 01 (2017-07-15)
Manual: The IP addresses of the MDU and computer must be in the same
network segment, and must be different.
Automatic: The MDU automatically queries available IP addresses in the
connected network. Ensure that the MDU and PC are on the same network
segment.
IP address
Subnet mask
Gateway
Serial port baud rate
Serial port address
SNMP
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 MDU Commissioning Guide