Cabinet Design and EMC
12.2 Selection of Devices Required for Operating SINAMICS
12.2.3
Overcurrent Protection by Means of Line Fuses or Circuit-Breakers
The cables for the drive line-up power supply must be protected against overcurrent. LV
HBC, D-type, and DO-type fuses with a gL characteristic or suitable circuit-breakers can be
used.
Note
For use in networks capable of supplying a maximum of 36 kA rms at 480 Vac if the device
is protected by means of the UL-approved (JFHR2) semiconductor safety fuse specified in
the manual.
The devices have to be protected with semiconductor fuses in accordance with the Manual.
The following tables list the requirements regarding line fuses and circuit-breakers for the
Active Line Modules and Smart Line Modules.
Table 12-3
Requirements regarding line fuses and circuit-breakers for the Active Line Modules
16 kW
I
fuse
35 A
rated
I
0.2s
>180 A
fuse
I
4s
>130 A
fuse
I
10 s
>100 A
fuse
I
240 s
>60 A
fuse
Table 12-4
Requirements regarding line fuses and circuit-breakers for the Smart Line Modules
I
fuse
rated
I
0.2s
fuse
I
4s
fuse
I
10 s
fuse
I
240 s
fuse
See catalog D21.2
12-6
36 kW
80 A
>360 A
>260 A
>200 A
>135 A
5 kW
16 A
>70 A
>50 A
>42 A
>30 A
55 kW
125 A
>450 A
>350 A
>250 A
>200 A
10 kW
35 A
>100 A
>80 A
>65 A
>45 A
Equipment Manual Booksize Cold-Plate Power Sections
Manual, (GH4), Edition 06.2005, 6SL3097-2AJ00-0BP2
80 kW
160 A
>650 A
>505 A
>360 A
>280 A
16 kW
35 A
>180 A
>130 A
>100 A
>60 A
120 KW
250 A
>865 A
>675 A
>480 A
>380 A
36 kW
80 A
>360 A
>260 A
>200 A
>135 A