4 Firmware Drive Functions
4.13 Mounting functions
5625
PROG_SIGNAL_ON_DELAY
Pickup delay for variable signalling function
Unit:
Default:
–
0
5626
PROG_SIGNAL_OFF_DELA Y
Dropout delay for variable signalling function
Unit:
Default:
–
0
4-156
SINUMERIK 840D/SIMODRIVE 611 digital Descr. of Functions HLA Module (FBHLA) – 04.00 Edition
Minimum:
Maximum:
0
10 000
Input of pickup delay for setting of message if the monitored quantity exceeds
the threshold setting (with hysteresis) (see diagram under MD 5620, Fig. 4-19).
Note
Changing the settings in MD 5625: PROG_SIGNAL_ON_DELAY and
MD 5626: PROG_SIGNAL_OFF_DELAY affects a time watchdog that is al-
ready running. The monitor is initialized with the new time settings.
Minimum:
Maximum:
0
10 000
Input of dropout delay for resetting of message if the monitored quantity drops
below the threshold setting (with hysteresis) (see diagram under MD 5620, Fig.
4-19).
Note
Changing the settings in MD 5625: PROG_SIGNAL_ON_DELAY and
MD 5626: PROG_SIGNAL_OFF_DELAY affects a time watchdog that is al-
ready running. The monitor is initialized with the new time settings.
Cross ref.: –
Relevant for:
Protection level:
HLA
3/3
Data type:
Effective:
UNS.WORD
Immediately
Cross ref.: –
Relevant for:
Protection level:
HLA
3/3
Data type:
Effective:
UNS.WORD
Immediately