Additional measures
Finely stranded, braided copper cables have to be routed in parallel with the cable shields in
the following cases:
● Old installations with already existing unscreened cables
● Cables with poor high-frequency properties
● Installations with bad grounding systems
The connections in the figure below provide a solid, high-frequency bonding between the
motor housing, the motor terminal box, the gearbox, the driven machine and the EMC
busbar.
Figure 4-2
Power Module PM230, IP20 / Push through
Hardware Installation Manual, 03/2012, A5E03448282B AA
Additional high-frequency bonding of the drive system
Connecting
4.2 EMC compliant connection
33