Operational Power And Voltage Derating; Current Reduction Depending On Pulse Frequency - Siemens SINAMICS G120P Hardware Installation Manual

Power module pm230, ip20 / push through
Hide thumbs Also See for SINAMICS G120P:
Table of Contents

Advertisement

6.2.3

Operational power and voltage derating

6.2.4

Current reduction depending on pulse frequency

Table 6- 12
LO base
load
1)
Power Module PM230, IP20 / Push through
Hardware Installation Manual, 03/2012, A5E03448282B AA
Current reduction depending on pulse frequency
Output base-load current at pulse frequency of
2 kHz
4 kHz
kW
A
A
0.37
--
1.30
0.55
--
1.70
0.75
--
2.20
1.1
--
3.10
1.5
--
4.10
2.2
--
5.90
3.0
--
7.70
4.0
--
10.20
5.5
--
13.20
7.5
--
18.00
11.0
--
26.00
15.0
--
32.00
18.5
--
38.00
22
--
45.00
30
--
60.00
37
--
75.00
45
--
90.00
55
--
110.0
75
--
145.0
90
--
178.0
The permissible motor cable length also depends on the cable type and the chosen pulse
frequency.
6 kHz
8 kHz
10 kHz
A
A
1.11
0.91
0.78
1.45
1.19
1.02
1.87
1.54
1.32
2.64
2.17
1.86
3.49
2.87
2.46
5.02
4.13
3.54
6.55
5.39
4.62
8.67
7.14
6.12
11.22
9.24
7.92
15.30
12.60
10.80
22.10
18.20
15.60
27.20
22.40
19.20
32.30
26.60
22.80
38.25
31.50
27.00
51.00
42.00
36.00
63.75
52.50
45.00
76.50
63.00
54.00
93.50
77.00
66.00
123.3
101.5
151.3
124.6
Technical specifications
6.2 Derating data
1)
12 kHz
14 kHz
A
A
A
0.65
0.59
0.85
0.77
1.10
0.99
1.55
1.40
2.05
1.85
2.95
2.66
3.85
3.47
5.10
4.59
6.60
5.94
9.00
8.10
13.00
11.70
16.00
14.40
19.00
17.10
22.50
20.25
30.00
27.00
37.50
33.75
45.00
40.50
55.00
49.50
--
--
--
--
--
--
16 kHz
A
0.52
0.68
0.88
1.24
1.64
2.36
3.08
4.08
5.28
7.20
10.40
12.80
15.20
18.00
24.00
30.00
36.00
44.00
--
--
51

Advertisement

Table of Contents
loading

Table of Contents