Technical specifications
Common performance ratings of the Power Module
Feature
Line voltage
Output voltage
Input frequency
Output frequency
Power factor λ
Line impedance
Inrush current
Pulse frequency
(factory setting)
Electromagnetic compatibility
Braking methods
Protection level
Storage temperature
Operational temperature
Operational altitude
Operational voltage
Humidity
Environmental requirements
Pollution
Shock and vibration
Electromagnetic radiation
Short Circuit Current Rating
(SCCR)
Over-voltage category
1)If fuse-protected with a listed Class J or 3NE1 fuse, rated voltage 600 V AC with the rated current of the specific
converter.
42
Specification
3 AC 380 V ... 480 V ± 10%
3 AC 0 V ... input voltage * 0.95 (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 Hz ... 650 Hz, depending on the control mode
0.9
Uk ≤ 1 %, a line reactor must not be used
Less than rated input current
4 kHz
Can be increased up to 16 kHz (up to 8 kHz for 55 kW, 75 kW) in 2 kHz steps.
Increasing the pulse frequencies leads to an output current reduction.
Filtered Units are suitable for environmental classes category C2 in accordance with
IEC61800-3: 2004. For details, see the Hardware Installation Manual, Appendix A2
(Page 57).
DC braking
IP20 built-in units
-40 °C ... +70 °C (-40 °F ... 158 °F)
see Operational temperature and temperature derating (Page 50)
see Operational altitude and altitude deratings (Page 50)
See Operational power and voltage derating (Page 51)
< 95% RH - non-condensing
Protected according to environmental class 3C2 to EN 60721-3-3 against damaging
chemical substances
According pollution degree level 2
Do not install the inverter in an environment which contains atmospheric pollutants such
as dust and/or corrosive gases.
Do not drop the inverter or expose to sudden shock. Do not install the inverter in an area
where it is likely to be exposed to constant vibration. See also Permissible shock and
vibration values (Page 52).
Do not install the inverter near sources of electromagnetic radiation.
65 kA
1)
Supply circuits:
non-supply circuits:
Over-voltage category III
Over-voltage category II
Power Module PM230, IP20 / Push through
Hardware Installation Manual, 03/2012, A5E03448282B AA