Tubing Data For Cooling And Heating Tank; Paw-Vp380L - Panasonic PAW-VP1000LDHW Installation Manual

Air-to-water heat pump systems, domestic hot water system for r410a and r32 use
Hide thumbs Also See for PAW-VP1000LDHW:
Table of Contents

Advertisement

Tubing Data and Refrigerant
4.2

Tubing data for cooling and heating tank

4.2.1 PAW-VP380L

4
30
Indoor Unit
PAW-VP380L
Tubing data
Tubing size outer diameter
Refrigerant connection pipe
Indoor unit pipe junction
Outdoor unit pipe junction
Wall thickness of the insulation
Limit of tubing length (L)
Height differential of Indoor/
Outdoor units (H1)
Systems must be pre-charged with refrigerant
Required additional refrigerant over 7,5 meters
Refrigerant charged at shipment R410A
Liquid tube
[mm (inch.)]
Gas tube
[mm (inch.)]
Liquid tube
[mm (inch.)]
Gas tube
[mm (inch.)]
Liquid tube
[mm (inch.)]
Gas tube
[mm (inch.)]
Liquid tube
Gas tube
Outdoor unit is placed higher
Outdoor unit is placed lower
DHW PAW-VP - Installation manual – 2020-05
Outdoor Unit
U-200PE2E8A
Ø 9.52 (3/8)
Ø 22.22 (7/8)
Ø brazing 12.7 (1/2)
Ø brazing 19.05 (3/4)
Ø flared connection 12.7 (1/2)
Ø flared connection 19.05 (3/4)
[mm]
>10
[mm]
>19
[m]
30
[m]
30
[m]
30
[kg]
1
[g/m]
45
[kg]
4.2