Detailed Settings For Indoor/Outdoor Unit Cz-Rtc5B/Rtc4/2; Setting Flow Chart - Panasonic PAW-VP1000LDHW Installation Manual

Air-to-water heat pump systems, domestic hot water system for r410a and r32 use
Hide thumbs Also See for PAW-VP1000LDHW:
Table of Contents

Advertisement

8.1.4 Detailed settings for indoor/outdoor unit CZ-RTC5B/RTC4/2

The new value must be set during the commissioning.

8.1.5 Setting Flow Chart

The system is in a fault-free state so that a safe commissioning can take place. All valid rules
have been followed.
!
Important
To follow exactly the described steps at the following flow chart is mandatory.
No.
Action
1
2
3
4
5
6
7
8
9
10
11
12
DHW PAW-VP - Installation manual – 2020-05
Check Indoor Unit
Turn Power "ON"
Initialization
Start Indoor Unit Detail Setting
Set Indoor Unit
"DN" code 10 & 11
Restart Detail Setting and set
other Indoor Unit "DN" codes
Finish Indoor Unit
"DN" code setting
Initialization
Start Outdoor Unit Detail Setting
Set Outdoor Unit "DN" codes
Finish Outdoor unit
"DN" code setting
Reset Power supply
How to make Settings
Note
Check if all temperature sensors are correctly
connected. All jumpers/bridged plugs (if any)
according to the wiring diagram, power supply and
communication wires are connected as shown in the
electrical wiring diagram.
Wait until initialization is finished.
Described at pages before:
Setting Procedure for Remote Controller Model
CZ-RTC5B
Attention:
After the setting "DN" 10 & 11 go out of detailed
setting:
Follow described at pages before:
Setting Procedure for Remote Controller Mode
CZ-RTC5B
See corresponding "DN" code list described on the
following pages, (combination for combination) for
Indoor Unit.
Described at pages before:
Setting Procedure for Remote Controller Model
CZ-RTC5B
Wait until initialization is finished.
Described at pages before: Detailed Setting Procedure
for Remote Controller Model CZ-RTC2 / CZ-RTC4
See corresponding "DN" code list described on the
following pages (combination for combination) for
Outdoor unit.
Described at pages before: Detailed Setting Procedure
for Remote Controller Model CZ-RTC2 / CZ-RTC4
After restart Power supply and Initialisation is finished,
proceed commissioning.
8
61

Advertisement

Table of Contents
loading

This manual is also suitable for:

Paw-vp750ldhwPaw-vp380l

Table of Contents