System drawings

5
5.1

System PACi DHW

5
32
System drawings
Standard system 1:1
without water circulation
Standard system 1:1
with water circulation pipe*
External Pump control
example:
Water flow:
Qmin = 1 ltr./minute
Water pump operation
schedule:
At night: ON 15 min
OFF 80 min
Through the day:
ON 15 min
OFF 40 min
For a hotel or apartment complex where the last room is more than 30 meters away from the
DHW tank, a water pump (for example type Grundfos comfort UP 15-14 BA PM) should be
installed in order to obtain hot water quickly.
Remember to install a return pipe pump circulation of maximum Ø15 mm and make sure that
supply and return pipes are well insulated for minimal heat loss.
Outdoor unit
City Water in
Outdoor unit
DHW PAW-VP - Installation manual – 2020-05
DHW
DHW tank
City
Water
in
DHW tank
DHW