For a hotel or apartment complex where the last room is more than 30 meters away from the
DHW tank, a water pump (for example type Grundfos comfort UP 15-14 BA PM) should be
installed in order to obtain hot water quickly.
Remember to install a return pipe pump circulation of maximum Ø15 mm and make sure that
supply and return pipes are well insulated for minimal heat loss.
City Water in
DHW tank
Qmin = 1 litre/minute
Water pump operation schedule
City Water in
DHW tank
PAW-VP•LDHW - Technical Manual – 2019-11
DHW
DHW
At night
ON
15 min
OFF 80 min
Through the day ON
15 min
OFF 40 min