Error Codes PACi & ECOi
10 Error Codes PACi & ECOi
10
108
Alarm codes for indoor/outdoor units PACi
Alarm Code
Alarm Meaning
E01
Remote controller reception error
E02
Remote controller transmission error
E03
Error in indoor unit receiving signal from remote controller (central)
Error in indoor unit receiving signal from the outdoor unit. No communication from the outdoor unit for 3 minutes
E04
E05
Abnormal indoor/outdoor communication error
E06
Outdoor unit failed to receive serial communication signals from indoor unit
E08
Dublicate indoor unit address settings error
E09
More than one remote controller set to main error
E12
Automatic address setting start is prohibited while auto-address setting in progress.
E14
Main unit dublication in simultaneous-operation multi control (detected outdoor unit)
E15
Automatic address alarm (the total capacity of indoor units is too low)
Automatic address alarm (the total capacity of indoor units is too high or the total number of indoor units is too many)
E16
E18
Faulty communication in group control wiring
E20
Connection problem of indoor/outdoor units
F01
Abnormal refrigerant sensor liquid return (E1) indoor unit
F04
Compressor discharge temperature sensor (TD) trouble
F06
Inlet temperature sensor (C1) in heat exchanger trouble intermediate
F07
Temperature sensor (C2) in heat exchanger trouble outdoor air temperature
F08
Sensor (TO) trouble
F10
Abnormal water inlet/outlet sensor (TA) indoor unit
F12
Compressor inlet suction temperature sensor (TS) trouble
F31
Outdoor unit nonvolatile memory (EEPROM) trouble
H01
Primary (input) Overcurrent detected
H02
PAM trouble
H03
Primary Current CT sensor (current sensor) failure
H31
HIC trouble
L04
Outdoor unit address duplication
L10
Outdoor unit capacity not set or invalid
L13
Indoor unit type setting error
L18
4-way valve operation failure
P03
Compressor dicharge temperatue trouble
P04
High pressure trouble
P05
AC power supply trouble
P13
Alarm valve open
P14
O2 sensor detect
P15
Insufficient gas level detected
P16
Compressor overcurrent trouble
P22
Outdoor unit fan motor trouble
P29
Lack if INV compressor wiring, INV compressor actuation failure (including locked), DCCT failure
P31
Group control error
PAW-VP•LDHW - Technical Manual – 2019-11