Panasonic PAW-VP1000LDHW Technical Manual page 105

Air-to-water heat pump systems, domestic hot water system for r410a and r32 use
Hide thumbs Also See for PAW-VP1000LDHW:
Table of Contents

Advertisement

Tank controller CZ-RTC5B detailed settings
Parameter
10
11
16
2C
Outdoor unit detailed settings by RTC2/4
Parameter
20
21
4E
4F
42
A5
Tank controller CZ-RTC5B detailed settings
Parameter
0B
0C
0D
10
11
16
2C
2D
Outdoor unit detailed settings by RTC2/4
Parameter
35
36
Tank controller CZ-RTC5B detailed settings
Parameter
10
11
2C
Outdoor unit detailed settings by RTC2/4
Parameter
4E
4F
Tank controller CZ-RTC5B detailed settings
Parameter
11
2C
PAW-VP•LDHW - Technical Manual – 2019-11
U-250PZH2E8 / PAW-VP1000LDHW
Default value
New value to set
0031
0031
0012
0023
0015
0000
0000
0006
Default value
New value to set
-015
-035
180
600
000
+005
000
+005
-002
000
000
030
ECOi U-10ME2E8 ECOi U-16MF3E8 / PAW-VP1000LDHW PAW-VP750LDHW
Default value
New value to set
0000
0001
0000
0001
0000
0001
0030
0031
0012
0023 / 0018
0015
0000
0000
0000
0000
0010
Default value
New value to set
000
-005
000
-005
U-200PZH2E8 / PAW-VP380L
Default value
New value to set
0031
0031
0012
0021
0000
0006
Default value
New value to set
000
+005
000
+005
U-200PE2E8 / PAW-VP380L
Default value
New value to set
0012
0021
0000
0002
How to make Settings
Explanation
Water unit
Indoor capacity type 250
No fan
No expansion valve
Explanation
Th. Off differential change from 1.5 k to 3.5 k
Th. Off judging time in sec.
Condensing temperature lower limit
Condensing temperature upper limit
Condensing temp. offset from -2 k to 0 k
Frost adherence temp. change from -2 °C to -4 °C
Explanation
02 sensor
Display of cold wind prevention
Auto mode cooling/heating
Water unit
Indoor capacity type 140
No fan
Expansion valve present
Operating mode setting
Attention: add jumper to EXCT CN073 (red) supplied with PCB
Explanation
Condensing temp. Offset from 0 k to 5 k
Condensing temp. Offset from -2 k to 5 k
Explanation
Water unit
Indoor capacity type 200
No expansion valve
Explanation
Condensing temperature lower limit
Condensing temperature upper limit
Explanation
Indoor capacity type 200
No expansion valve
Check and adjust
Check and adjust
Check and adjust
Check and adjust
Check and adjust
9
Check and adjust
Check and adjust
105