Installation

Refrigerant Piping

Cut the pipes
- Use the accessory piping kit or the pipes
purchased locally.
- Measure the distance between the indoor
and the outdoor unit.
- Cut the pipes a little longer than measured
distance.
Burrs removal
- Completely remove all burrs from the cut
cross section of pipe/tube.
- Put the end of the copper tube/pipe to
downward direction as you remove burrs in
order to avoid to let burrs drop in the tubing.
Pipe brazing
- Always make sure to flow Nitrogen at
0.2kgf/cm
2
within the pipe while brazing.
- If the brazing is done without flowing
Nitrogen, it can generate a thick oxidized
coating within the pipe to interfere with normal
operation of valve and compressor etc.
Insulation
- Use insulation material with high thermal
resistance and rated for the anticipated
operating temperature range.
- When installed in humid environment, use
thicker insulation material as specified by
system designer.
Classification
Liquid pipe(Ø9.52)
Gas pipe(Ø22.2, Ø15.88)
20 Hydro Kit
Thickness
t9 or above
t19 or above
Copper
tube
90°
Point down
Direction of Nitrogen
Copper tube
Taping
Inside product
Slanted Uneven Rough
Pipe
Reamer
Regulator
Valve
Nitrogen
Nitrogen
Nitrogen
Panel
Insulation
Copper