3.1 Installation Precautions

To ensure the optimal operating condition and longest service life, install the NetCol5000-C
correctly as required.
Figure 3-1 Maintenance space
Issue 07 (2020-03-16)
Check whether the environment meets the requirements before installation, and whether
reconstruction is needed for routing pipes and cables.
Install the NetCol5000-C according to the design drawing and reserve space for
maintenance.
Reserve more than 1200 mm maintenance space at the front or rear of the smart cooling
product and more than 1000 mm maintenance space at the other end.
more than 1200 mm maintenance space at the front door and more than 1000 mm
maintenance space at the rear door as an example.
Install the water inlet and outlet pipes to the predefined paths and reserve proper length
for connecting water inlet and outlet pipes.