Step 5 Set the value to 300 Pa for the new differential pressure switch. Install it in the reverse order
of
Step 2
Step 6 Power on the device, tap Start on the LCD home screen. Choose Settings > Alarm
Settings > Main Board. Check that Air filter blocked is Allow.
Step 7 Choose Maint > Diagnostic Mode > Enter, and set Indoor fan to 100%.
Step 8 Block 100% air volume at the return air side using a plastic foam board or baffle plate, and
check whether the Air filter blocked alarm is generated. If so, the differential pressure switch
works properly. Then exit the diagnostic mode.
----End

6.4.7 Replacing the T/H Sensor

Prerequisites
Context
Preparation: Maintain from the rear door.
Procedure
Step 1 Tap Shutdown on the LCD home screen.
Exercise caution because the device is still energized after it is shut down on the LCD.
Step 2 Open the rear door and remove the air filter.
Step 3 Remove the cable terminals from the RS485_IN and RS485_OUT ports on the T/H sensor.
Step 4 Pull out the T/H sensor upwards.
Issue 07 (2020-03-16)
to
Step
4. Close the rear door after the installation.
The temperature and humidity (T/H) sensor needs to be replaced.
A spare T/H sensor of the same model is available and functional.