Mitsubishi Electric MELSEC iQ-R Series Quick Start Manual page 34

Servo system, simple motion module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

1.
1. Set [Pr.82 Forced stop valid/invalid selection] to "1: Invalid".
[Pr.82 Forced stop valid/invalid selection] is set to "valid" as default for safety. Since the machine does not use
forced stop, change it to "1: Invalid".
2. Set the "Input type" in [Pr.116 FLS signal selection], [Pr.117 RLS signal selection], [Pr.118 DOG signal
selection], and [Pr.119 STOP signal selection].
Select "15: Invalid" since the machine does not use Data set method, FLS, RLS, and STOP for home position
return.
Set common/basic/detailed/home position return/expansion parameters where necessary.
(Refer to Appendix 2 for setting examples.)
3 POSITIONING CONTROL STARTUP
32
3.3 Parameter Settings for Simple Motion Module
2.
1.
3.
2.
4.