ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) 23
Operation diagram
A1-A2
2830 Ω
1100 Ω
R [Ω]
19 Ω
12 Ω
Test / Reset
S1-T2
11-14 / 21-24
11-12 / 21-22
1
Tripping caused by overtemperature
2
Control supply voltage interrupted
3
Test (outputs are switched off)
4
Short-circuit in sensor circuit
5
Reset (resets fault)
• Manually with a front-face Test / Reset button
• Externally by a remote reset between terminal S1-T2
■
DOLD MK 9163N.12/110-ATEX thermistor relay
Layout
A1 (+)
11
21
P1
P2
X1
R
Test /
Reset
22
24
X2
12
14
A2
1
1
2
A1-A2
Power supply
P1-P2
Measuring circuit with 1...6 sensors
X1-X2
Remote reset push button switch
11-12/14
Output contacts (1)
• 11: Common
• 12: Normally-closed
• 14: Normally-open
21-22/24
Output contacts (2)
• 21: Common
• 22: Normally-closed
• 24: Normally-open
Test / Reset
Test and internal reset button
Upper LED
Supply voltage present
(green)
"R" LED (red)
Fault (overtemperature, broken wire, or short-circuit in the
sensor circuit)
5
5
3
5
4
5